Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05121
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2006 | ROBERT SHERRY | WATER | REVIEW | Denied | Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pd |
| 10/02/2006 | DAVE MANN | FIRE | REVIEW | Approved | 1. Fire sprinklers are required in group R. IFC Section903.2.7 2. Bedroom does not emergency egress. |
| 10/03/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/05/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/05/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/10/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Clarify restroom facility location for the F-1 occupancies. 2) Clarify firewall at room 1 along property line. 3) Clarify distance from property line on northeast wall of room 1 and room 3. 4) Provide bond beams per structural calculations for fire wall. Engineer shall stamp drawings for firewall on permit set. |
| 10/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 10/19/2006 | STEVE SHIELDS | ZONING | REVIEW | Denied | No permits are to be issued until the lot split has be completed. |
| 10/24/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | NO WASTEWATER PLUMBING FIXTURES ADDED |