Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05120
Parcel: 116162700

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05120
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2006 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pd
10/02/2006 DAVE MANN FIRE REVIEW Approved
10/03/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/05/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/05/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Clarify restroom facility location for the F-1 occupancies.
2) Clarify firewall at room 1 along property line.
3) Clarify distance from property line on northeast wall of room 1 and room 3.
4) Provide bond beams per structural calculations for fire wall. Engineer shall stamp drawings for firewall on permit set.
10/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
10/19/2006 STEVE SHIELDS ZONING REVIEW Denied No permits are to be issued until the lot split has be completed.
10/24/2006 GERRY KOZIOL WWM REVIEW Passed NO WASTEWATER PLUMBING FIXTURES ADDED