Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05100
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/20/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 09/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/21/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify which air handler is serving which space in the tenant area. The common ventilation calculation applies to multiple areas served by the same air handler. |
| 09/21/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a drinking fountain per Section 2900, IBC 2003. |
| 09/21/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/26/2006 | GBONILL1 | WATER | REVIEW | Needs Review | |
| 09/26/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 09/26/2006 | GBONILL1 | WWM | REVIEW | Needs Review |