Permit Number: T06CM05084
Parcel: 126010290

Address:
4237 E KILMER ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05084
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Based on the fixture units from Table 6-5, UPC 2003, a 100' developed length, an assumed lift of 8', and the water pressure range (45 - 63 PSI) provided by the architect, the a 5/8" meter with a ¾" water service pipe is inadequate to supply the existing and new fixtures. Recheck the calculations and revise the drawing as required. Reference Sections 610.4, 610.7, 610.8, and Appendix A, UPC 2003.
2. Provide a riser diagram of the water distribution piping for the house. Clarify the connection pints for the new piping and indicate where the pipe is underground and above ground. Reference Section 103.2.3, UPC 2003.
3. Provide upper terminal cleanouts per Section 707.4, UPC 2003 and a building sewer cleanout at the junction of the new building drain to the new building sewer per Section 719.1, UPC 2003.
4. Show how the gas pipe is to be run to the gas range. Reference Section 103.2.3, UPC 2003.
5. Provide shower and tub/shower control valves that comply with the requirements of Section 420.0, UPC 2003.
6. Indicate the size of the vent for the water heater and detail the termination of the vent. Reference Section 510, UPC 2003.
7. Provide listing information for the clothes dryer to show that a 3" diameter exhaust duct is allowed. Reference Section M1501.2, IRC 2003.
11/22/2006 DAVE WITT BUILDING-RESIDENTIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
11/28/2006 SUE REEVES REJECT SHELF Completed