Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2006 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T06CM05084

11/03/06 4237 E. KILMER ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



FOUNDATION PLANS:

1. PLEASE SHOW THE FOOTINGS. THIS APPEARS TO BE A CAP ON THE SLAB BUT SECTION A-A SHOWS THE BEAMS UPHOLDING THE ROOF ARE GONE. IF THE WALLS WILL BE BEARING, PROVIDE FOOTINGS.IF THE POST AND BEAM SYSTEM WILL USE THEIR FOOTINGS, PLEASE ILLUSTRATE THE BEAM AND FOOTING AND NOTE THE POST / BEAM WILL UTILIZE THE EXISTING FOOTINGS.

2. PLEASE PROVIDE A LANDING AT THE MASTER BEDROOM'S 6070 SGD. PLEASE SEE R311.4.3 .

FLOOR PLANS:

1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

2. PLEASE NOTE THE SHOWER WALLS ARE TO BE PROTECTED TO NOT LESS THAN 6 FEET ABOVE THE FLOOR . SEE R307.2 .

SECTIONS - DETAILS - MISC. NOTES:

1. PLEASE PROVIDE A CROSS SECTION OF AN INTERIOR WALL ILLUSTRATING THE CONNECTIONS.

PLUMBING PLANS:

1. PLUMBING IN ACCORD WITH THE INTERNATIONAL PLUMBING CODE WILL BE REVIEWED BY ROBERT SHERRY.





MECHANICAL PLANS:

1. THE SUPPLY AND RETURN AIRS APPEAR TO BE UNDERSIZED. PLEASE JUSTIFY. SEE M1403.1

2. RETURN AIRS AREN'T PERMITTED TO BE LOCATED IN KITCHENS. SEE M1602.2 .

3. WHAT SIZE ARE THE HEAT STRIPS?

4. MECHANICAL GENERAL REQUIREMENTS, NOTE 6 / A5 ; PLEASE INCLUDE CITY APPROVAL FOR CHANGES.

5. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. PLEASE PROVIDE A RECEPTACLE IN THE HALLWAY. SEE E3801.10

2. HOW DO THE CLOSET LIGHT FIXTURES LOCATED 6" FROM THE NEAREST STORAGE COMPLY WITH E3903.11?

3. PLEASE PROVIDE A RECEPTACLE FOR THE PENINSULAR COUNTER TOP. SEE E3801.4.3 .

4. PLEASE PROVIDE A RECEPTACLE ON THE DINING ROOM SIDE OF THE NARROW WALL COMMON WITH THE FAMILY ROOM BAR SINK.

5. THE RECEPTACLES BETWEEN THE OVEN AND THE KITCHEN SINK APPEAR TO BE OVER SPACED. SEE E3801.4.1 .

6. CIRCUIT 9,SERVING THE KITCHEN TOPS @ THE PENINSULA, MAY SERVE THE DINING ROOM BUT NOT THE GREAT ROOM. SEE E3603.2 .

7. CIRCUIT 2 , SERVING THE KITCHEN TOPS MAY NOT SERVE THE RECEPTACLE NEAR THE FAMILY ROOM BAR SINK. SEE E 3602.2 .

8. CIRCUIT 1A , SERVING THE MASTER BATH RECEPTACLE ISN'T PERMITTED TO SERVE THE OUTDOOR RECEPTACLE. E 3603.4 .


OUTDOOR LIGHTING CODE:

1. PLEASE CHECK THE LUMENS PERMITTED BY LIGHTING CODE TABLE 5.1 . THE E3 AREA PERMITS 55,000 LUMEN PER ACRE, 12,000 OF WHICH MAY BE NOT SHIELDED.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
11/03/2006 GERRY KOZIOL WWM REVIEW Approved
11/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide an approved appeal to the building official allowing the International Residential Code (2003) to be used in lieu of the Uniform Plumbing Code (2003) for the plumbing design.