Permit Number: T06CM05080
Parcel: 13602002Q

Address:
8178 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T06CM05080
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2007 DAVE MANN FIRE REVIEW Approved
09/25/2007 HEATHER THRALL ZONING HC SITE REVIEW Denied Please see zoning review comments
09/25/2007 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department Plans Coordination Office
FROM: Heather Thrall, Senior Planner
PROJECT: T06CM05080, 8178 E. 22nd Street, New Auto Repair facility
Commercial Site Plan, 3rd Review

TRANSMITTAL DATE: July 20, 2007

COMMENTS: Please resubmit revised drawings and a response letter, stating how Zoning Review Section comments for LUC & DS were addressed.

1. (Per last review) Per DS 2-02.2.1.7, for records/ inspections, LIST REQUIRED/provided setbacks for this project. Staff verifies no setback issues present.

2. (Per last review) Per DS 2-02.1.1.12, per DS 2-08, due to re-design of the plan:
A) 5' wide pedestrian refuge area - striped - is permitted only in areas not generally accessed by public. Provide concrete sidewalk from office entry along front of building (west side) up to area where transitions to garages (see redlines)
B) Provide a ramp where transitioning from sidewalk to asphalt refuge area.
C) Provide truncated domes on ramps to signify change from pedestrian to vehicular area
D) Connect disabled pkg access aisle across parking lot to accessible route (see redlines)

3. Please note, depending upon responses provided, further review comments may be forthcoming. For any questions, contact me Heather.Thrall@tucsonaz.gov or 837-4951.

HCT C:\planning\site\DSD\T06CM05080 8178 e 22nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan
09/27/2007 ANDREW CONNOR NPPO REVIEW Approved
09/27/2007 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond
10/15/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: October 15, 2007
SUBJECT: 22nd Street Automall
TO: Bright/Kliman
LOCATION: 8178 E. 22nd St., T14S, R15E, Section 21, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T06CM05080 (Third Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed building plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. The following items need to be addressed prior to the next submittal:


Site Plan:

1. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. For a PAAL at the stem street side and an arterial as the through street side the near side site visibility triangle should be 345' and the far side site visibility triangle should be 125'. Site visibility triangle (SVT) indicated in detail B2 - Sheet C5.1 indicate the SVT's on site plan shows east triangle as 345'. Please verify that the site visibility triangles meet the requirements for the conditions of the site. Future site visibility triangle does not appear to be aligned properly. Please verify location and label. Current label indicates two existing site visibility triangles. Label the appropriate triangle as future.

2. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. DS Sec.2-02.2.1.A.14: Provide (label and dimension) the required onsite maneuvering area for the loading zone that is shown adjacent to the proposed building. Refer to AASHTO for the national standards for turning radii. 3nd request.

3. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Existing PAAL access to proposed trash dumpster does not meet minimum 24' for two way traffic aisle or minimum 20' for fire access. See D.S. 3-05.2.1.C.1 for traffic aisles. Also clarify if access easement will allow adequate spacing for solid waste vehicle.

4. Per 40' back up dimension refuge truck does not appear to meet clearance. Current location and positioning of trash enclosure does not permit for adequate maneuverability of the refuge truck.



Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
10/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the site drawing to include the following information:
a. the location of the main water lines and fire hydrants
b. the location of any gas piping or gas meters
c. the location and size of the public sanitary sewer
d. The proposed point of connection to the sanitary sewer
e. the location, invert, and rim elevation of all manholes and cleanouts
Reference City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.
2. Comment not addressed. Provide the first floor elevation of the proposed building. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/23/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
10/23/2007 GERARDO BONILLA REJECT SHELF Completed