Permit Number: T06CM05077
Parcel: 117141970

Address:
49 W KENNEDY ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05077
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2007 DANIEL RUSCH BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM05077


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.


All dimensions and notes shall be consistent on each plan or elevation.


FLOOR PLANS:

1. Projections shall not extend to a point closer than 2 feet from the property line, and when extending into the 3-foot fire separation distance shall have not less than one-hour fire-resistive construction on the underside. Indicate compliance with R302.1. Justify 1-hour fire rating for "galvanized metal siding". Just because it is not combustible doesn't qualify it as a fire rated barrier.
2. SEE notes for rigid foam insulation on addition and comply.


ELECTRICAL PLANS:

1 See electrical notes for addition, as they are inter-twined.


If you have any questions, please contact your assigned plans examiner Daniel Rusch at 791-5550, extension 1113.