Permit Number: T06CM05062
Parcel: 125121770

Address:
3302 E 3RD ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM05062
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied October 31, 2006

Sierra Pacific Homes
3333 North Campbell Avenue, Suite 12
Tucson, AZ 85719

RE: SIERRA PACIFIC MODEL 3931 REVISION – 1st REVIEW
CITY OF TUCSON LOG NO. T04CM05062-R, P05-M0056-R
WILLDAN PROJECT NO. 13890-6065

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 2003 IBC, 2003 IMC, 2003 IECC, 1997 UAC, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
N/A N/A N/A N/A N/A N/A

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
Reviewed and accepted.

ARCHITECTURAL COMMENTS:
Not part of this review.

STRUCTURAL COMMENTS:
Truss Design Drawings
Please coordinate the bearing conditions between the truss design drawings and the approved plans for trusses M07-13 and M18-20 per section 106.1.1 of the 2003 IRC as the cantilevered conditions shown on the trusses appear longer than indicated on the plans.

Please coordinate the bearing condition between the truss design drawings and the approved plans for truss GR01 per section 106.1.1 of the 2003 IRC, as the plans indicate the truss continuing over an exterior bearing wall, but the truss design drawing does not indicate an interior bearing point.

PLUMBING COMMENTS:
Not part of this review.

MECHANICAL COMMENTS:
Not part of this review.

ELECTRICAL COMMENTS:
Not part of this review.

ENERGY CODE COMMENTS:
Not part of this review.

ACCESSIBILITY COMMENTS:
Not part of this review.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
11/07/2006 GERRY KOZIOL WWM REVIEW Denied needs to show clothes washer w/ plumbing.
needs WW 8th floor credit evaluation-740-6500

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2006 DELMA ROBEY OUT TO CUSTOMER Completed
11/16/2006 SUE REEVES REJECT SHELF Completed