Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T06CM05057
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/24/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/24/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/24/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/28/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |