Permit Number: T06CM05053
Parcel: 116162700

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05053
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2006 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pd
10/03/2006 MARTIN BROWN FIRE REVIEW Denied 1. Fire sprinklers are required in group R. IFC Section903.2.7
2. Bedroom does not have emergency egress.
10/04/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide water supply isometrics. Reference Section 103.2.3, UPC 2003.
3. Provide waste and vent isometrics. Reference Section 103.2.3, UPC 2003.
4. Provide equipment data for the water heater. Reference Section 103.2.3, UPC 2003.
5. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC
6. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 504.7, IECC 2003.
7. Provide underground facility tracer wires for any new, underground, exterior piping per ARS 40-360.22.
8. Provide fixture descriptions for all plumbing fixtures. Reference Section 401.1, UPC 2003.
9. Provide shower and tub/shower control valves that comply with the requirements of Section 420.0, UPC 2003 and Section 504.6.1, IECC 2003.
10. Specify the materials to be used for the water piping and fittings. Reference Section 604.0, UPC 2003.
11. Show the location of the CW shut off valve for the building service entrance. Reference Section 605.2, UPC 2003.
12. Show the size, route, and termination of the T&P relief pipe from the water heater. Reference Section 608.5, UPC 2003.
13. Provide water pressure and water pipe sizing calculations. Reference Section 610.1, UPC 2003.
14. Specify the materials to be used for the drainage piping and fittings. Reference Section 701.0, UPC 2003.
15. Provide a schedule of waste fixture units for all plumbing fixtures using the values shown in table 7-3, UPC 2003. Include the total number of each fixture being installed. Reference Section 703.1, UPC 2003.
16. Resize the vent piping to conform to Table 7-5 and Section 904.1, UPC 2003. Reference Section 703.2, UPC 2003
17. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference Section 707.4, UPC 2003.
18. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees. Reference Section 707.5, UPC 2003.
10/04/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide supporting documentation for the assembly U-factors for the adobe walls along with the SHGC for the windows. Reference Section 104.2, IECC 2003.
2. Show how the evaporative cooler is being supplied with water and how the unit is to be drained. Reference Section 304.1, IMC 2003.
3. Provide an auxiliary drain pan for the evaporative cooler. Reference Section 307.2.3 IMC 2003.
4. Show how the occupied spaces are being maintained at a minimum temperature of 68°F on a design heating day (32°F). Reference Sections 309.1 and 312.1, IMC 2003.
5. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference 401.5, IMC 2003.
6. Show the size, route, and termination of the dryer exhaust duct. Specify the material of construction for the dryer exhaust duct. Reference Sections 504.1, 504.2, and 504.4, IMC 2003.
7. Specify the materials of construction for the rigid and flexible ductwork. Reference Section 603, IMC 2003.
8. Specify the grilles and diffusers. Reference Section 603.17, IMC 2003.
10/10/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied City of Tucson Structural Plans Examiner - Christy Foreman E-mail - Christy.Foreman@tucsonaz.gov
SITE PLAN:

1. Show all driveways, sidewalks, steps and fences. Clarify access to residential units.
2. Indicate the location of gas, water, electric and sewer or septic line on the property, and where they enter the building. Provide the location of your water meter and septic system if it exists.

FOUNDATION PLANS:

1. Dimension the wall thickness, footing width thickness and depth into undisturbed soil for each footing type and condition.

2. All slabs and pads, including landings at all doors, shall be shown and their thickness specified.

3. All exterior doors require a landing or floor at the exterior. Landings must be at least as wide as the doors they serve and 36" in the direction of travel.

FLOOR PLANS:

1. Provide access to each separate attic and under floor space that exceeds 30SF. Designate locations on the drawings. Openings shall not be less than 22"X30" for attics, or 18"X24" for under floor space. Attic access shall provide a minimum of 30" of headroom, and shall be located in a hallway or readily accessible space.
2. Individual dwelling units in duplexes must be separated by a 1 hour fire wall from floor to bottom of roof sheathing.
3. The walls and soffit of the enclosed space under stairs shall be protected on the enclosed side with ½" gypsum board R314.8.
4. Note that bathtub and shower enclosures shall be finished per P2710 with ceramic tile, or a listed enclosure, to a height of 72" above the drain per R702.4 and R307.2.

5. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per R307.2 (figure).
6. Detail and specify stair width (minimum 36"), rise and run (minimum 10" tread depth and 7 ¾" maximum riser height per R314), landing width (per R312), handrail heights (per R315), guardrail height (per R316) and intermediate rail spacing (per R316).

16. Identify ceiling heights in all areas on floor plan. If sloped ceiling, note average height.

STRUCTURAL PLANS:
1. Provide structural calculations to justify floor framing and details.

ELEVATIONS:
1. Provide complete drawings of all elevations. It appears window is missing on elevation for bedroom/loft.
2. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.

Fire Protection:
1. Specify fire sprinkler system per 903.2.7 IBC 2003.
2. Specify smoke alarm per 907.2.10.1.2.
10/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Label each room. For example bedroom, kitchen, bathroom. Plans Examiner will determine compliance with Article 210 of the NEC after this has been done.
2. Provide panel and circuit number for each electrical load.
3. Provide panel schedule(s) and feeder load calculations.
4. Plot the location of the electrical service on scaled drawing.
5. Provide service load calculations.
6. Provide electrical line diagram.
7. Provide fault calculations for all new electrical panels.
8. Provide a lighting fixture schedule.
9. For any lighting pole exceeding 20' in height, provide detail and calculations for pole and foundation, on the plans, sealed by a Structural Engineer registered in the State of Arizona.
10. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.

THIS IS AN INCOMPLETE REVIEW. PLANS NOT SUFFICIENTLY DEVELOPED. SEE THE ABOVE COMMENTS AND THE ATTACHED "ELECTRICAL PERMITTING REQUIREMENTS."
10/19/2006 STEVE SHIELDS ZONING REVIEW Denied Unable to approve until the lot split is approved.
10/24/2006 GERRY KOZIOL WWM REVIEW Approved