Permit Number: T06CM05012
Parcel: 11102032B

Address:
3115 E PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05012
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
09/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the plans as required to clarify how the exhaust duct will comply with Section 506.3.10, IMC 2003.
2. Second request. Provide a manufacturer's cut sheet showing that the hood is listed for airflow less than that required by Section 507.13.2, IMC 2003.
3. The existing exhaust fan installation may not comply with current code. Provide plans to show that the installation of the exhaust fan complies with the requirements of Sections 501.2, 506.3.12, 506.5.2, 506.5.4, and 506.5.5, IMC 2003.
10/10/2006 DROBEY1 ENGINEERING REVIEW Passed NO ENGINEERING NEEDED PER JASON GREEN

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2006 DELMA ROBEY APPROVAL SHELF Completed
10/10/2006 DELMA ROBEY OUT TO CUSTOMER Completed
10/10/2006 DELMA ROBEY REJECT SHELF Completed