Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM05012
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/21/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the plans as required to clarify how the exhaust duct will comply with Section 506.3.10, IMC 2003. 2. Second request. Provide a manufacturer's cut sheet showing that the hood is listed for airflow less than that required by Section 507.13.2, IMC 2003. 3. The existing exhaust fan installation may not comply with current code. Provide plans to show that the installation of the exhaust fan complies with the requirements of Sections 501.2, 506.3.12, 506.5.2, 506.5.4, and 506.5.5, IMC 2003. |
| 10/10/2006 | DROBEY1 | ENGINEERING | REVIEW | Passed | NO ENGINEERING NEEDED PER JASON GREEN |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/10/2006 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 10/10/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 10/10/2006 | DELMA ROBEY | REJECT SHELF | Completed |