Permit Number: T06CM05012
Parcel: 11102032B

Address:
3115 E PRINCE RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T06CM05012
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the enclosing shaft for the grease duct to provide a minimum separation of 6" between the duct and the shaft. Show how the shaft will be framed. Reference Section 506.3.10, IMC 2003.
2. Provide a manufacturer's cut sheet showing that the hood is listed for airflow less than that required by Section 507.13.2, IMC 2003.
3. The design exhaust flow is 300 CFM greater than the makeup air flow. Show how this complies with the requirements of Section 508.1, IMC 2003.
4. Provide plans to show that the installation of the exhaust fan complies with the requirements of Sections 501.2, 506.3.12, 506.5.2, 506.5.4, and 506.5.5, IMC 2003.
09/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/15/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/15/2006 DAVE MANN FIRE REVIEW Approved