Permit Number: T06CM04993
Parcel: 133361990

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04993
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied January 29, 2007

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701

RE: DAILOUS ARIZONA ROOM– 2nd REVIEW
CITY OF TUCSON LOG NO. T06CM04993
WILLDAN PROJECT NO. 13881-6070

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter third review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.”

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
R-3 N/A V-B 362 N/A N/A

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
All Sheets
NEW COMMENT: Lettering should be a minimum of 1/8” high. Reference the City of Tucson Submittal Requirements.

ARCHITECTURAL COMMENTS:
Reviewed and accepted.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Reviewed and accepted.


MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Sheet 5
Indicate the location of all disconnecting means for air conditioning and heating units, air handlers, compressors, and disconnects. Reference IRC Section E4001.5 and Table E4001.5. COMMENT REMAINS: Not addressed.

Indicate on the plans that a minimum of 30” X 36” clear working space will be provided in front of all panels, cabinets, and disconnects. Reference IRC Section E3305.2. COMMENT REMAINS: Not addressed.

Show on the plans that the service outlet will be within 25’ of HVAC equipment. Reference IRC Section E3801.11. COMMENT REMAINS: Not addressed.

NEW COMMENT: Please provide cut sheets for the outdoor lighting and cross-reference with calculations. Reference the City of Tucson Outdoor Lighting Code.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb