Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM04993
Parcel: 133361990

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM04993
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied November 8, 2006

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701

RE: DAILOUS ARIZONA ROOM– 1ST REVIEW
CITY OF TUCSON LOG NO. T06CM04993
WILLDAN PROJECT NO. 13881-6070

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Jim Stanley.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
R-3 V-B 362

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
General
Please note at the time of the second review, additional permit fees and inspections will be required.

ARCHITECTURAL COMMENTS:
Reviewed and accepted.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Reviewed and accepted.


MECHANICAL COMMENTS:
Sheet 5
Note on plans: “Mechanical shall comply with 2003 IRC Chapters 12-24.” Reference IRC Section M1201.2.

If the heating or air conditioning equipment is located in the attic, show location of access, catwalk, and working platform. Show provisions for and route of secondary condensate drain. Reference IRC Sections M1305.1.3 and M1411.3.

Flues connected to more than one appliance shall be not less than the area of the largest connector plus 50% of the additional connectors. Typical water heater: 3” flue; furnace: 4” flue. Show on plans. Reference IRC Section M1805.3.

For gas burning appliances, please provide combustion, ventilation, and dilution air requirements. Reference IRC Section G2407.1.

Show on the plans how mechanical fresh air will be provided if using one of the non-vented roof methods. Reference Non-Vented Roof Details Dated 7/18-19/2001.

Please specify if heat pump is gas. Provide the length of the branch BTU demand total developed length from water to appliance.

ELECTRICAL COMMENTS:
Sheet 5
Note the location, clearance, type, amperage, and disconnect of the service panel. Note the grounding and bonding method. Reference IRC Sections E3507, E3508, and E3509.

Indicate the location of all disconnecting means for air conditioning and heating units, air handlers, compressors, and disconnects. Reference IRC Section E4001.5 and Table E4001.5.

Indicate on the plans that a minimum of 30” X 36” clear working space will be provided in front of all panels, cabinets, and disconnects. Reference IRC Section E3305.2.

Indicate the location of convenience outlet(s), light switch(es), and a disconnect for attic heating and air conditioning equipment. Service outlet must be within 25’ of the equipment. Reference IRC Sections M1305.1.3.1, E3801.11, and E3803.4.

Show on the plans that the service outlet will be within 25’ of HVAC equipment. Reference IRC Section E3801.11.

Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used. Reference IRC Section E4001.6.

Clarify the location and access to any sub-panel. Reference IRC Section 106.1.1.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
11/16/2006 SUE REEVES REJECT SHELF Completed