11/20/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied November 20, 2006

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701

RE: CUSTOM PLUS PLAN # 1976 – 2nd REVIEW
CITY OF TUCSON LOG NO. T06CM04913
WILLDAN PROJECT NO. 13881-6055

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
SFR
Garage
Patio N/A V-B 1976
615
296 No Smoke

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
Truss calculations

GENERAL COMMENTS:
General
NEW COMMENT: A deferred submittal letter for truss calculations will need to be forwarded directly to the Building Official and approved. Reference the City of Tucson Submittal Policy.

ARCHITECTURAL COMMENTS:
Reviewed and accepted.

STRUCTURAL COMMENTS:
Sheet 3
Locate and identify brace wall types and locations, along with the appropriate nailing schedule. Reference IRC Section R106.1.1. COMMENT REMAINS: Not addressed.

Sheet 5
Indicate and note post size, double or triple studs, and coordinate with foundation plan. Reference IRC Section R106.1.1. COMMENT REMAINS: Not addressed.

Detail all brace wall connections from the foundation to the roof plywood. Reference IRC Section R106.1.1. COMMENT REMAINS: Not addressed.

PLUMBING COMMENTS:
Sheet 9
Show the required clean-outs. Reference the City of Tucson Submittal Requirements. COMMENT REMAINS: Not addressed.

Waterline: Provide the total fixture unit demand (based on Tables 6-4 & 7-3 or Tables L-1 & L-2) and the maximum developed length. Reference UPC Section 610. COMMENT REMAINS: Not addressed.

Sheets 1 and 9
The City of Tucson has adopted the 2003 Uniform Plumbing Code with local amendments. All plans must reference the 2003 UPC with local amendments in its entirety. COMMENT REMAINS: Not addressed.

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Reviewed and accepted.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.