Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T06CM04893
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/12/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | CDRC TRANSMITTAL FROM: Michael St.Paul, Planning Technician PROJECT: T06CM04893 879 West Paseo De Los Zonjeros PAD 10: Menlo Park, Mercado District, Lot 24 TRANSMITTAL: September 12, 2006 COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. The plot plan as presented cannot be approved at this time. Please revise and resubmit the plot plan. 2. The address has been provided on the coversheet. In addition, please provide the address for this townhouse on the site plan. 3. The plot plan provided does not depict the stairs provided with the loft option above the garage. Please revise the plan. 4. The elevation drawings only depict the stairway from one side. Please revise the elevation drawings to show the stairway from both sides. 5. Please have MDDRC review the revised plans. 6. Please be aware that there may be additional comments relative to changes in the plans submitted. |
09/12/2006 | MICHAEL ST. PAUL | NPPO | REVIEW | Needs Review | |
09/25/2006 | WILDAN | 2ND PARTY REVIEW | REVIEW | Denied | September 22, 2006 City of Tucson Development Services 201 N. Stone Avenue Tucson, AZ 85701 RE: MENLO PARK LOT 24 – 1ST REVIEW CITY OF TUCSON LOG NO. T06CM04893 WILLDAN PROJECT NO. 13881-6052 The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable. This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan. Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya. Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms SFR Garage N/A III-B 2726 550 No Smoke Special Inspection is required for the following items: Concrete Structural Masonry Field and shop welding Masonry The following items are acceptable for deferred submittals: N/A GENERAL COMMENTS: General A signed special inspection form from the City of Tucson is required at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy. All Sheets All lettering should be a minimum of 1/8 “ high capitalized. Reference the City of Tucson Submittal Requirements. ARCHITECTURAL COMMENTS: Sheets 3.1 and 3.2 Show fireplace location, hearth size, and materials. For factory built or zero clearance fireplaces, provide cut sheets, make, model number, and the approval number of the approved testing agency. Specifications are not required to be on plans. Factory built fireplaces shall comply with UL-127. For masonry fireplaces, show cross-section. Reference IRC Section R1003.1. Sheet 4.2 For veneer, note and specify type of veneer. Provide detail and specify anchoring method, backing, vapor barrier, and support. Reference IRC Sections R301.2.2.3.1 and R703.7. STRUCTURAL COMMENTS: Sheet 3.1 Provide stairway connection details and stringer sizes. Pre-fabricated metal stair shall have manufacturer’s specifications attached to plans. Reference IRC Section R106.1.1. Sheet S2 All slabs and pads, including landings at all doors, shall be shown and their thickness specified. Reference IRC Sections R506.1 and 403.1. Indicate the slope for exterior slabs. Reference IRC Section R311.6.1. PLUMBING COMMENTS: Sheet P3 Plumbing vents shall be a minimum of 10 feet away from all air intakes. Reference UPC Section 906.2. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down. Reference UPC Section 608.5. Note that bathtub and shower enclosures shall be finished with ceramic tile, or an approved nonabsorbent surface, to a height of 72” above the drain. Reference IRC Section R307.2 and UPC Sections 412.7 and 412.8. MECHANICAL COMMENTS: Sheet M1.2 The exhaust fan schedule specifies three exhaust fans and on the floor plan four are indicated. Please clarify. Reference IRC Section 106.1.1. ELECTRICAL COMMENTS: Sheet E3 Note the location, clearance, type, amperage, and disconnect of the service panel. Note the grounding and bonding method. Reference IRC Sections E3507, E3508, and E3509. Provide an exterior outlet at grade level located at both the front and back of the dwelling. These outlets shall be GFCI protected. Reference IRC Sections E3801.7 and E3802.3. Indicate on the plans that a minimum of 30” X 36” clear working space will be provided in front of all panels, cabinets, and disconnects. Reference IRC Section E3305.2. Note that light fixtures in clothes closets shall be installed in accordance with IRC Section E3903.11. Note on plans: “All branch circuits that supply 125-volt, single-phase, 15- and 20-ampere outlets installed in dwelling unit bedrooms shall be protected by an arc fault circuit interrupter listed to provide protection for the entire branch circuit.” Reference IRC Section E3802.11. Please provide cut sheets for all the exterior light fixtures shown or noted on Model plans. The cut sheets need to provide lumens per fixture and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. For non-Model plans, please provide cut sheets and calculations for all exterior lighting fixtures. Reference the City of Tucson Outdoor Lighting Code. Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference the City of Tucson Submittal Requirements. ENERGY CODE COMMENTS: Sheet P3 Provide a note that water heaters with vertical pipe risers shall have a heat trap on both the inlet and outlet of the water heater, unless the water heater has an integral heat trap or is part of a circulating system. Reference IECC Section 504.7. Sheet M1.2 Annotate on the plans that any ductwork installed in unconditioned space will have a minimum of R-5 insulation, and any ductwork installed outside the building envelope will have a minimum of R-8 insulation. Reference IRC Section N1103.32. ACCESSIBILITY COMMENTS: Reviewed and accepted. Sincerely, WILLDAN Martin Haeberle, C.B.O. Building Official MAH/tb |
10/06/2006 | GERRY KOZIOL | WWM | REVIEW | Denied | needs dsc 1st floor hold harmless letter for connection to an on-site private sewer #PT05S04298 which connects to a public sewer G-05-002 which has not been accepted & released by PCWWM |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/16/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
10/16/2006 | SUE REEVES | REJECT SHELF | Completed |