Permit Number: T06CM04838
Parcel: 10821018X

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM04838
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/27/2006 ROBERT SHERRY WATER REVIEW Denied 1. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. The applicable rules from the Arizona Board of Technical Registration regarding the use of seals (Title 4, Chapter 30, Article 3, R4-30-304) require the registrant to seal, sign, and date (The date the document was sealed.) the drawing. See http://www.btr.state.az.us/
10/31/2006 DAVE MANN FIRE REVIEW Approved
11/06/2006 GERRY KOZIOL WWM REVIEW Approved