Permit Number: T06CM04835
Parcel: 132091500

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04835
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2006 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied October 19, 2006 CITY OF TUCSON - SECOND CHECK
Tucson Appl. No. T06CM04835
Bureau Veritas Job No. 01006-161037

Carlos Melgoza
2610 E. Norton Vista
Tucson, AZ 85713


Re: Plan Review: Melgoza Residence
Address: 2718 E. Norton Vista

Bureau Veritas Company, has completed a review of the following documents on behalf of the City of Tucson:

1. Plans: Two (2) sets of plans (9 sheets, 2 through 9) no dates or stamps.

2. Structural Calculations: None submitted.

Energy Code Compliance: None submitted.

Miscellaneous Documents: None submitted.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas



Kevin Askeland
Residential Plans Examiner











KA:pc c:/tucson\01006-161037pc2
enclosures

Re: Stories: One
Occupancy R-3
Fire Sprinklers: No
Building Area (sq. ft.): 1601 (livable)
638 (porch)
407 (garage)
2646 Total

A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

COMMENTS:


Provide two (2) sets of corrected plans.
Provide gas ISO IRC chapter 24 (under plumbing section).

FLOOR PLAN:


Provide the following note: A separate insulation inspection prior to drywall or an insulation certificate will be required at time of final. IRC Section N1101.3.1.

ELEVATIONS:

Provide height dimensions for roofline, headers, top plate and finished floor. IRC Section R106.


FOUNDATION PLAN


Foundation plates and sills shall be bolted to the foundations with minimum ½ inch bolts at 6 feet of less on center and embedment a minimum 8 inches into the foundations. IRC Section R304.1.6.

Locate and specify all anchor bolt spacing and post anchors on the foundation plan.

FRAMING PLAN:

Specify lumber grade, species and size of members. IRC Section R602.

TRUSSES SYSTEMS: Trusses can be submitted as a “Deferred Submittal” for custom homes only. However, they mush be submitted and approved prior to their fabrication.


Specify all hangers used to hang trusses from girder trusses, walls, or other locations. IRC
Sections R802 & ANTSI-TPI 1995.

Show how trusses are to carry roof mounted or attic mounted HVAC units. Are trussed
designed for 10 p.s.f. non-current live load and 10 p.s.f. dead load on bottom chord?

The architect and engineer of record must review truss calculations (when applicable).
Truss calculations must bear a shop drawing stamp showing this review has been done.

MECHANICAL PLAN


Show condensate line and secondary condensate line. IRC Section M14113 and M1411.3.1. Drainage.

PLUMBING:

Provide note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. IRC Section P3008.

If you have any questions regarding the above comments, please contact Shelley Knuffle at (520) 622-9220 between 8:00 A.M. to 5:00 P.M., M-F.