Permit Number: T06CM04832
Parcel: 14023116C

Address:
5943 S MORRIS BL

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T06CM04832
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2006 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied September 12, 2006 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T06CM04832
Bureau Veritas Job No. 01006-161038

Benjamin Figueroa
5943 Morris Blvd
Tucson, AZ 85706


Re: Plan Review: Figueroa Residence
Address: 5943 Morris Blvd

Bureau Veritas Company, has completed a review of the following documents on behalf of the City of Tucson:

1. Plans: Two (2) sets of plans (9 sheets, 1 through 9) no dates or stamps.

2. Structural Calculations: None submitted.

Energy Code Compliance: None submitted.

Miscellaneous Documents: None submitted.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas



Shelley Knuffke
ICC Plans Examiner











SK:pc c:/tucson\01006-161038pc1
enclosures

Re: Stories: One
Occupancy R-3
Fire Sprinklers: No
Building Area (sq. ft.): 1222 (livable)


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

FLOOR PLAN:

Indicate the location of the T and P relief line from the water heater to the exterior of the building. Note the T and P relief line to be full size steel pipe or hard drawn copper tubing extending to the exterior of the building and terminating in a downward position not more than 2 feet or less than 6 inches above grade. The T and P relief line shall not terminate over walkways, patios, carports or other similar areas. IRC Section P2803.6.1.

Provide the following note: A separate insulation inspection prior to drywall or an insulation certificate will be required at time of final. IRC Section N1101.3.1.

PLUMBING:

Note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. IRC Section P3008.

ELECTRICAL:

Note and specify that at least one 20-amp branch circuit shall be installed to serve the laundry room and this circuit shall have not other outlets. NEC Article 210-52(f) and IRC Sections E3603.3..

Receptacle outlets for ranges and clothes dryers shall be a 3-pole with ground type. Four-wire, grounding-type flexible cords will be required for connection of ranges and clothes dryers. The bonding jumper shall not be connected between the neutral terminal and the frame of the appliance. IRC Section E3808.

In kitchen and dining rooms, a receptacle outlet shall be installed at each wall counter space 12 inches or wider so that not point along the wall is more than 24 inches from a receptacle outlet and shall be GFCI protected. IRC Section E3801.4.1. Right of sink.

Fixtures, fittings, boxes and receptacles located in damp or wet locations shall be “listed” to be suitable for such location. IRC Sections E3805.10, E3902.9, E3903.8


If you have any questions regarding the above comments, please contact Shelley Knuffle at (520) 622-9220 between 8:00 A.M. to 5:00 P.M., M-F.
09/18/2006 ANDREW CONNOR NPPO REVIEW Denied Submit Application for Exception per DS 2-15.0; include acceptable documentation such as photographs, which clearly indicates that the project will not impact Protected Native Plants.
09/27/2006 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: T06CM04832
5943 S. Morris Blvd., New Single Family Residence
Residential Site Plan Review

TRANSMITTAL DATE: September 27, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Please increase all type font size to 12 point to ensure the plan can be microfilmed.

2. To clarify how this lot is accessed, revise the plan to include the two lots to the west, as access is across those lots - give easement information and show Morris Boulevard.

3. Zoning staff determined the lot on which this residence is proposed has not been legally created through the required City of Tucson review process - only recorded through Pima County. This lot is the result of a split of subdivided land from one original lot into three. The number of splits mandates, at minimum, that this project be reviewed by the Community Design Review Committee (CDRC) for a possible Record of Survey. A final plat may be required if other divisions determine that process is needed. Submit a copy of the proposed lot splits for preliminary presubmittal review to the CDRC office (201 N. Stone, contact Marilyn Kalthoff at 791-5608x1117 should you require assistance on the CDRC submittal). Once the presubmittal review and conference are done and the project is allowed to proceed, the actual Record of Survey documents shall be submitted to the CDRC office for full staff review. Once the CDRC review is completed, zoning review staff may then be able to resume review of the project. - Provide a copy of the Record of Survey on the resubmittal.

4. As an advisement, on preliminary review, staff did not find any setback, height or lot coverage issues. Staff will do a more thorough review with relation to access, etc. upon completion of the Record of Survey. For the residence, a counter review is possible.

5. Should you have any questions on my review, please contact me via email at Heather.Thrall@tucsonaz.gov or at 791-4541x1156.

HCT C:\planning\site\DSD\T06CM04832 5943 S. Morris sfr.doc
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
10/02/2006 GERRY KOZIOL WWM REVIEW Denied 1: NEEDS TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER
2: NEEDS WASTEWATER 8TH FLOOR REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER
10/10/2006 JASON GREEN ENGINEERING REVIEW Denied DATE: October 10, 2006
SUBJECT: Single Family Residence- Site Plan Review
TO: Benjamin Figueroa
LOCATION: 5943 S Morris Blvd, T15S R14E Sec07, Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T06CM04832


SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed single-family residence site plan. The site plan is not approved at this time. Please address the following comments:


SITE PLAN COMMENTS:

1) DS Sec.2-02.2.0: Revise the site plan to increase all type font to the equivalent of 12 point to assure that the lettering is legible when reproduced or when photographically reduced for record keeping purposes.
2) DS Sec.2-02.2.1.20: Provide on the proposed site plan the recordation information associated with the 16' ingress/egress and utility easement for Parcels B and C.
3) DS Sec.2-02.2.1.A.17: Provide cut and fill quantities on the proposed site plan for grading plan purposes.
4) DS Sec.2-03.11.1: Per Zoning review comments a Record of Survey must be applied for and approved prior to site plan approval. Record of Survey applications can be obtained through the Community Design Review Committee (CDRC). Submit a copy of the proposed lot splits for preliminary pre-submittal review to the CDRC office, 201 N Stone Ave; contact Marilyn Kalthoff at 791-5608x1117 should you require assistance on the CDRC submittal. Once the pre-submittal review and conference are done and the project is allowed to proceed, the actual Record of Survey documents shall be submitted to the CDRC office for full staff review. Once the CDRC review is completed, engineering review will be able to resume review of the project. Provide a copy of the Record of Survey on the resubmittal.


GENERAL COMMENTS:

Please provide an approved Record of Survey and a revised site plan that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon resubmittal of the site plan.

For any questions or to schedule a meeting, call me at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2006 GERARDO BONILLA APPROVAL SHELF Completed
10/18/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
10/18/2006 GERARDO BONILLA REJECT SHELF Completed