Permit Number: T06CM04818
Parcel: 125073360

Address:
431 N PLUMER AV

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM04818
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved Client informed she needed to get detail and plans specifying new roof. Include roof section specifying materials and nailing specification. Clarify drainage for roof. Once this information has been provide a o.k. to submit will be provided. With structural calculations this is not a walk through project.
01/04/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04818 10/10/06

Provide electrical plans for the work cited on violation t06vl00719, and for any other unpermited electrical work.
10/10/2006 DAVE MANN FIRE REVIEW Approved
11/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the specifications (mechanical and electrical) for the new rooftop A/C unit.
2. Show the type and resistance of the duct insulation.
3. Provide the balancing data for the A/C unit.
4. Show the size, route, and termination of the condensate drain for the A/C unit.
5. Show how the rainwater is directed around the supports for the A/C unit.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2007 CINDY AGUILAR OUT TO CUSTOMER Completed