Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T06CM04818
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | Client informed she needed to get detail and plans specifying new roof. Include roof section specifying materials and nailing specification. Clarify drainage for roof. Once this information has been provide a o.k. to submit will be provided. With structural calculations this is not a walk through project. |
| 01/04/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 10/10/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04818 10/10/06 Provide electrical plans for the work cited on violation t06vl00719, and for any other unpermited electrical work. |
| 10/10/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the specifications (mechanical and electrical) for the new rooftop A/C unit. 2. Show the type and resistance of the duct insulation. 3. Provide the balancing data for the A/C unit. 4. Show the size, route, and termination of the condensate drain for the A/C unit. 5. Show how the rainwater is directed around the supports for the A/C unit. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |