Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04814
Parcel: 107111280

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T06CM04814
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 226 W. Delano St.
T06CM04814, T06CM04816 & T06CM04817
Site Plan (1st Review)

TRANSMITTAL DATE: October 20, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) & Land Use Code (LUC).

2. There appears to have been an addition to Unit #2. The last approved site plan and the 2005 aerial differ from what is shown on the provided site plan. Please clarify.

3. Show all utilities to each unit on the site plan.

4. Zone will provide an over the counter review at the request of the applicant. Call or email for an appointment.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\site\t06cm04814.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
10/20/2006 SSHIELD1 NPPO REVIEW Passed
10/27/2006 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation
11/16/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM04814 (Unit #1)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

SITE PLAN:

1. Indicate the location of electric service (meter) on the property.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code.

ELECTRICAL PLANS:

1. Show the location of the panel, E3501.6.2. Panelboard access requires 30"wide x 36"deep clear working space, E3305.2. Panelboards may not be located in clothes closets or bathrooms, E3305.4.
2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3304.11 & E3606.2. Identify outlet devices requiring replacement.
3. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch to be replaced or added, E3603.5.
4. Cables shall be protected with conduit where subject to physical damage, E3702.3.2.
5. Receptacle outlets shall be installed in habitable spaces so that no point along the wall (exclude door openings) is more than 6' from a receptacle outlet, E3801.2.
6. Note that two or more 2O AMP small appliance circuits shall be provided to serve kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room. Such circuits shall not serve other rooms, E3603.2 and E3801.3 through E3801.4.5.
7. All receptacle outlets serving kitchen countertops shall have ground fault circuit interrupting protection. Label each receptacle GFCI requiring such protection, E3802.6.
8. A receptacle outlet shall be provided within 3' of the basin in each bathroom, E3801.6. Bathroom receptacles shall be on a separate 20 AMP circuit with no other outlets, E3603.4.
9. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3.
10. Note that an arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.11.
11. Provide a note indicating only approved outlet boxes shall be used for ceiling fans, E4001.6.
12. Show locations of smoke detectors, R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. This includes existing bedrooms with attic space, R313.1.1.
13. Smoke alarms are required outside each separate sleeping area, R313.1.2.


If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
12/06/2006 SUE REEVES REJECT SHELF Completed