Permit Number: T06CM04803
Parcel: 123090270

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM04803
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 LINHART PETERSEN POWERS ASSOC BUILDING-RESIDENTIAL REVIEW Denied December 28, 2006 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T06CM04803
Bureau Veritas Project No. 01006-161117
Mr. Michael Ramirez
3041 W. Calle Canario
Tucson, Arizona 85746


Re: Plan Review: Knipe Guest House
Address: 2808 E. Drachman Street



Dear Michael Ramirez:

Bureau Veritas North America has completed a review of the following documents on behalf of the City of Tucson:

Plans: Two (2) copies of plans (7 sheets) dated September 13, 2006 by Peter A. Petrowski.

Truss Calculations: None submitted for review.

Structural Calculations: None submitted for review.



These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.



Sincerely,

BUREAU VERITAS NORTH AMERICA



Randy McCoy
ICC Plans Examiner








RM:pc S:\Tucson\01006-1610117pc1.doc
Enclosures

Re: Stories: One
Building Area (sq. ft.): 960 (living area)
456 (porch/patio)
1416 Total sq. ft

A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

GENERAL REQUIREMENTS:
Provide an accurate index to drawings on the first sheet of the set.

FLOOR PLAN COMMENTS:
Note and specify that the shower area walls shall be finished with a nonabsorbent surface to a height of six feet above the floor. IRC Section 307.2.
Please indicate the location of the T and P relief line from the water heater to the exterior of the building. Note the T and P relief line to be full size steel pipe or hard drawn copper tubing extending to the exterior of the building and terminating in a downward position not more than 2 feet or less than 6 inches above grade. The T and P relief line shall not terminate over walkways, patios, carports or other similar areas. IRC Section P2803.6.1.
Provide the following note: A separate insulation inspection prior to drywall or an insulation certificate will be required at time of final. IRC Section N1101.3.1.
All habitable rooms shall be provided with aggregate glazing area of not less than 8 percent of the floor area of such rooms. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. IRC Section R303.1.

ELEVATION COMMENTS:
For thin coat stucco systems over foam board, note and specify the ICBO Evaluation Report number, system name and manufacturer. Note and specify the vapor barrier used.

FOUNDATION PLAN COMMENTS:
All slabs and pads, including landings at all doors, shall be shown and their thickness specified. Indicate the slopes for exterior slabs.

FRAMING PLAN COMMENTS:
Note on the plan all lumber shall bear an approved grading stamp.
Specify type of design and construction of all walls and partitions. Wood stud walls shall comply with prescriptive requirements of IRC Section R602 or shall be designed by an Arizona Registrant. Masonry and concrete basement walls shall comply with prescriptive requirements of IRC Section R404 or shall be designed by an Arizona Registrant. IRC Sections: R404, R601 & R602. 2X4 or 2X6
Specify design criteria: roof live and dead loads. IRC Section R301.
Provide complete floor (if applicable) and roof framing plans. Specify size and spacing of all framing members. Indicate all post sizes. IRC Section R106.
Indicate the size and span of headers in all bearing and non-bearing walls. IRC Sections R602.7 & R606.9.

TRUSS SYSTEMS: Trusses can be submitted as a “Deferred Submittal” for custom homes only. However, they must be submitted and approved prior to their fabrication.
Provide complete truss calculations and truss layout plan. Truss designs submitted must include all types and be designed for the loading conditions, span, slope, and spacing designated on the framing plan.
Truss calculations must be signed, dated and sealed by an Engineer who is registered in the State of Arizona.
The seal on the truss calculations shall be dated within the latest adopted IRC.
All truss calculations shall be cross-referenced to the truss layout or the roof and floor framing plans.

MECHANICAL COMMENTS:
Show condensate line and secondary condensate line. IRC Section M1411.3 and M1411.3.1.

PLUMBING COMMENTS:
Note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. IRC Section P3008.

ELECTRICAL COMMENTS:
Receptacle outlets for ranges and clothes dryers shall be a 3-pole with ground type. Four-wire, grounding-type flexible cords will be required for connection of ranges and clothes dryers. The bonding jumper shall not be connected between the neutral terminal and the frame of the appliance. IRC Section E3808.
Island or peninsular countertops 12 inches or wider shall have at least one receptacle outlet. NEC Article 210-52(c)2.
Provide a note indicating all branch circuits that supply 125-volt, single-phase, 15 and 20-ampere receptacle outlets installed in dwelling unit bedrooms shall be protected by an arc-fault circuit interrupter(s). NEC Article 210-12(b).


If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.
01/19/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2007 FSANCHE1 OUT TO CUSTOMER Completed
01/30/2007 SUE REEVES REJECT SHELF Completed