Permit Number: T06CM04796
Parcel: 12602016B

Address:
4639 E 1ST ST

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM04796
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2006 STEVE SHIELDS ZONING REVIEW Approved
10/05/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04796 10/5/06

1. Provide an electrical circuit for AC-5.
2. Identify the number 0f new 4/0 conductors are intended for the conduit run between the CT can and the New Disconnect, and between the new Disconnect and New Panel. Take care not to install a redundant ground on the line side of the service disconnect.
3. Show fault current rating of Existing Panel L.
10/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/09/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/09/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved