| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/05/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04796 10/5/06 1. Provide an electrical circuit for AC-5. 2. Identify the number 0f new 4/0 conductors are intended for the conduit run between the CT can and the New Disconnect, and between the new Disconnect and New Panel. Take care not to install a redundant ground on the line side of the service disconnect. 3. Show fault current rating of Existing Panel L. |
| 10/09/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/09/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/09/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |