Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/01/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 8-1-07 ACTIVITY NUMBER: T06CM04777 PROJECT NAME: TAQUERIA JENNY'S PROJECT ADDRESS: 6440 S. 6TH AVE ARCHITECT / ENGINEER: JESUS FLOREZ PROJECT REVIEWER: LeeRay Hanly TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. No response given to original correcton notes 1-13. Please be aware that additional corrections may be required for this project when new plans and structural calculations are submitted. Original correction notes follow. 1) 1997 Uniform Administrative Code - section 302.5 Inspection and Observation Program. When special inspection is required by Section 306, the architect or engineer of record shall prepare an inspection program which shall be submitted to the building official for approval prior to issuance of the building permit. The inspection program shall designate the portions of the work to have special inspection, the name or names of the individuals or firms who are to perform the special inspections and indicate the duties of the special inspectors. The special inspector shall be employed by the owner , the engineer or architect of record, or an agent of the owner, but not the contractor or any other person responsible for the work. When structural observation is required by Section 307, the inspection program shall name the individuals or firms who are to perform structural observation and describe the stages of construction at which structural observation is to occur. The inspection program shall include samples of inspection reports and provide time limits for submission of reports. 2) Clarify / justify occupant load and fixture count. 3) Provide code analysis and specify type of construction and allowable square footage. 4) It appears building and covered porch north wall is on property line. Please justify per section 704.11 parapets and section 705. 5) Provide / clarify accessible route from parking lot to restroom and service counter. See ANSI A117.1 2003. 6) Drinking fountain spout heights and water flow ANSI 602.4 and 602.6. 7) Wind exposure B should be used per section 1609.4. 8) Provide lateral analysis including exterior dining enclosure. 9) Provide structural calculations / justification for column design at exterior dining area. 10) Provide structural calculations to justify reinforcement of exterior dining area walls. 11) Clarify placement and structural support for mechanical equipment. 12) Provide reviewed and approved shop drawings for trusses or request a deferred submittal by letter from the Building Official. 13) 1611.2 Ponding instability. Roofs with a slope less than one-fourth-unit vertical in 12 units horizontal (2 percent) shall be investigated |
08/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | See comments from previous review. |
08/03/2007 | HEATHER THRALL | ZONING | REVIEW | Denied | zoning is unable to approve the building plans - dated 08/23/06 - until the site plan is approved for this project and the building plans are approved by the structural review division. |
08/16/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | No changes have been made to the previously submitted drawings. 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. The design of the building appears to include an unglazed opening in the east wall. This opening does not meet the requirements of Section 802, IECC 2003. Demonstrate compliance of the building envelope using ASHRAE/IESNA 90.1-2001. Reference Section 801.2, IECC 2003. 3. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference Section 104.2, IECC 2003. 4. Provide the installed weight of all of the rooftop equipment. Reference Section 106.3.1, IMC 2003. 5. Provide manufacturer's equipment data along with mechanical and electrical operating information for the evaporative cooler, furnace, Type I hood, makeup air system, and the exhaust fans. Reference Section 301.6, IMC 2003. 6. Provide structural calculations to verify that the roof is capable of supporting the dead load due to the installation of the roof top units and the grease hood. Reference Sections 302.1 and 507.6, IMC 2003. 7. If the pitch of the roof exceeds 3/12, provide service space for roof mounted equipment. Reference Section 306.6 IMC 2003. 8. Show how adequate access (i.e. walkways across the light gauge metal roof to the equipment service area) is being provided for the equipment located on the roof. Reference Section 306.5, IMC 2003. 9. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003. 10. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. 11. Provide a design for the installation of the Type I hood over the cooking or heat-producing appliances. Include balancing information, clearances, and details to show how the hood is supported from the building structure. Reference Section 507.2, IMC 2003. 12. Show the location of the barbecue and provide a Type I hood for it. Reference Sections 106.3.1 and 507.2, IMC 2003. 13. Provide make up air for the kitchen hood that complies with Section 508, IMC 2003. Reference Section 507.2, IMC 2003. 14. Provide a roof plan showing the locations of al of the roof top equipment and vents. Reference Section 106.3.1, IMC 2003. 15. Provide information to show how the ductwork has been sized. Reference Section 603.2, IMC 2003. |
08/16/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | No changes have been made to the previously submitted drawings. Indicate on the site utility plan the location of the reduced pressure backflow assembly, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
08/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | No changes have been made to the previously submitted drawings. 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide water isometrics and waste and vent isometrics. Reference Section 103.2.3, UPC 2003. 3. Provide equipment data for the water heater. Reference Section 103.2.3, UPC 2003. 4. Show slope of the building sewer line on drawing. Reference Section 103.2.3, UPC 2003. 5. Provide underground facility tracer wires per ARS 40-360.22. 6. Provide fixture descriptions (e.g. manufacturer and model number) for all plumbing fixtures. Reference Section 401.1, UPC 2003. 7. Provide a floor drain in the kitchen. Reference Section 412.2, UPC 2003. 8. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 9. Provide combustion air openings for the furnace. Reference Section 507, UPC 2003, as amended by the City of Tucson. 10. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003. 11. Clarify the plumbing note describing the heat traps: "Discharge shall be 8" from the floor and pointing downward." Reference Section 103.2.3, UPC 2003. 12. Clarify the nature of the appliance located next to the condiment table in the exterior eating area. Reference Section 103.2.3, UPC 2003. 13. Provide calculations showing how the water supply piping has been sized. Reference Sections 610.4 and 610.5, UPC 2003. 14. If any appliances (e.g. ovens, ice makers, soda dispensers, etc) are to be directly connected to the water supply system and do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2003 provide backflow prevention. Show the locations of any such appliances and specify the type of backflow protection assembly that is to be installed. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003. 15. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference Section 707.4, UPC 2003. 16. Provide indirect waste piping for the ice machine. Reference Section 801.2, UPC 2003. 17. Provide direct waste connections for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment. Reference Sections 304.0 and 801.2, UPC 2003. 18. Provide a vent to protect the grease trap from siphonage and backpressure. Reference Section 1002.1, UPC 2003. 19. Provide a vented flow control device for the grease trap. Reference Section 1014.3. UPC 2003. 20. Provide a cleanout downstream of the grease trap. Reference Section 707.8, UPC 2003. 21. Revise the detail of the grease trap shown on sheet P.1 to coordinate with the specified product. Reference Section 103.2.3, UPC 2003. 22. Provide information to show that the 2-way cleanout shown in the exterior eating area (sheets A.1 and P.1) complies with Sections 707.6 and 707.9, UPC 2003. 23. Provide information to show that the connection of the building sewer to the public sewer complies with the requirements of Pima County Wastewater (i.e. Wastewater Standard detail WWM 401, Revised 8/05). Reference Section 103.2.3, UPC 2003. 24. Show how stormwater is to be prevented from being introduced into the sanitary sewer by way of the mop sink. Reference Section 1101.2, UPC 2003. |
09/06/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | Building permit cannot be approved without approved site plan. See Site submittal for comments. -BCR (9/6/07) |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/17/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
09/17/2007 | CINDY AGUILAR | REJECT SHELF | Completed |