Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04735
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04735 8/23/06 1. Provide a lighting fixture schedule. 2. Provide rating of the bus of Panel N. 3. Provide fault current rating of Panel N. 4. Provide available fault current at Panel N. 5. Provide electrical line diagram. 6. Provide service load calculations. |
| 08/23/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the route and termination of the condensate drain. |
| 08/23/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a waste and vent riser diagram to show plumbing modifications. |
| 08/23/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/21/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 09/21/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 09/21/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 09/21/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/21/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/21/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |