Permit Number: T06CM04735
Parcel: 13329009A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04735
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04735 8/23/06

1. Provide a lighting fixture schedule.
2. Provide rating of the bus of Panel N.
3. Provide fault current rating of Panel N.
4. Provide available fault current at Panel N.
5. Provide electrical line diagram.
6. Provide service load calculations.
08/23/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the route and termination of the condensate drain.
08/23/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a waste and vent riser diagram to show plumbing modifications.
08/23/2006 ROBERT SHERRY WATER REVIEW Approved
09/21/2006 TERRY STEVENS ZONING REVIEW Approved
09/21/2006 DROBEY1 WWM REVIEW Needs Review
09/21/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/21/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
09/21/2006 MARTIN BROWN FIRE REVIEW Approved
09/21/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2006 DELMA ROBEY OUT TO CUSTOMER Completed