Permit Number: T06CM04719
Parcel: 14028035C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04719
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2006 HEATHER THRALL ZONING REVIEW Approved
08/23/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The operation of EF-1 for the new restroom will result in recirulation of air from the restroom. Reference Section 403.2.1, IMC 2003.
2. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2003.
3. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
08/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/23/2006 ROBERT SHERRY WATER REVIEW Approved
08/23/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide clear floor space for unisex and men's restroom per ansi A117.1 2003.
2) Provide work surface height and sink height in lounge per Ansi A117.1 2003.
3) Per chapt. 34 show breakdown on front sheet how 20% cost of construction is being spent towards accessibility. Include cost breakdown.
4) Clarify accessible path from parking lot to the restroom / primary function areas.
08/23/2006 GERRY KOZIOL WWM REVIEW Approved
08/23/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide water pressure calculations to support the water pipe sizing. Note that the water closet has a 1" CW supply on sheet P1, a ½" CW supply on sheet P3 and a 1-1/2" CW supply based on the pipe sizing chart. Reference Section 610.1, UPC 2003.
3. The 2-way cleanout shown in Detail 1/P3 is in violation of Section 707.6, UPC 2003.
08/23/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
08/23/2006 DAVE MANN FIRE REVIEW Approved
08/23/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review