Permit Number: T06CM04707
Parcel: 113060150

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM04707
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2006 GERRY KOZIOL WWM REVIEW Denied need 8th floor credit evaluation
09/19/2006 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T06CM04707

9/28/06 2250 E. KLEINDALE RD.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

4. ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE
RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF
THE STATE BOARD OF TECHNICAL REGISTRATION.

SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

2. PLEASE ILLUSTRATE THE PORCH AS A NEW PORCH (POCHE, OR STRIPE IN ACCORD WITH THE LEDGEND). ALSO, PLEASE CHECK THE AREAS USED FOR THE ADDITIONS (AND INCLUDE THE GARAGE) AND THE PORCH. THE PORCH SHOWN ON THE SITE PLAN DOESN'T REFLECT THE PORCH SHOWN ON THE FOUNDATION PLAN. IF THE EXTRA PORCH FOUNDATION IS FOR A FUTURE PROJECT, PLEASE NOTE THAT IT WILL BE UNDER A SEPARATE PERMIT AND SHOW IT ON THE SITE PLAN.

FOUNDATION PLANS:

1. WALL FOOTING SCHEDULE / A2 ; SHOULD NOTES 2 AND 3 BE ONE NOTE ?

2. PROVIDE A LANDING FOR THE MAN DOOR FI THE GARAGE. SEE R311.4.3

3. PLEASE DIMENSION THE LOCATIONS OF THE PORCH FOOTINGS

4. PROVIDE FOOTINGS FOR THE POSTS THAT SUPPORT THE PORCH ROOF.

FLOOR PLANS:

1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS ( SEE R303), AS WELL AS THE LOCATIONS OF TEMPERED GLASS PER R308.1 AND R308.4.

2. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS. SEE R310

- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.0SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

4. COMPLY WITH R309.2. PROVIDE ½" GYPSUM BOARD ON ALL WALLS COMMON TO THE GARAGE AND HOUSE.
NOTE DOORS BETWEEN HOUSE AND THE GARAGE SHALL BE MINIMUM 1-3/8" SOLID CORE, SELF-CLOSE, PER R309.1

5. COMPLETE THE DIMENSIONING OF THE FLOOR PLAN.

6. SHOW THAT EACH WATER CLOSET IS LOCATED IN A CLEAR SPACE NOT LESS THAN 30" WIDE AND HAS A
CLEAR SPACE IN FRONT OF NOT LESS THAN 24" PER R307.2 (FIGURE).

7. PROVIDE A FLOOR PLAN WITHOUT THE "NOT IN THIS PERMIT" OR AT LEAST BETTER DEFINE THE WALL THAT WILL BE THE EXTERIOR WALL. SHOW THE DOORS AND WINDOWS FOR THIS WALL. ASK THE ENGINEER TO REVIEW THE NEW FLOOR PLAN. THE DELETION OF THOSE ROOMS DELETED SOME OF HIS WALLS SO HE MAY HAVE TO REVISE HIS CALCULATIONS.

8. WHAT'S THE PLAN FOR THE PORCH FOUNDATION BEYOND THE FOUNDATION THAT'S ROOFED? IF IT'S FOR A FUTURE ROOF, NOTE THAT IT WILL REQUIRE A FUTURE PERMIT. IS THE BEAM AND FOOTINGS FOR THE PORCH FRAMING ON THIS PERMIT SIZED TO CARRY THE ADDITIONAL ROOF IN THE FUTURE? ALSO, THE POST HARDWARE FOR THE ADDITIONAL PORCH WILL REQUIRE PRESSURE TREATED, OR EQUAL, POSTS IN THE ABSENCE OF THE 1"CLEARANCE OF THE END GRAIN ABOVE GRADE. DO YOU WANT THE "CBQ" POST BASE INSTALLED NOW? THE POST BASES FOR THE FUTURE PORCH WILL BE DANGEROUS WITHOUT SOME PRE-CAUTIONARY MEASURES.

9. PLEASE SHOW THE ADDITIONAL PORCH ON THE SITE PLAN.

10. ASK MR. HARRIS TO LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS FOR THE AMENDED FLOOR PLAN. PROVIDE NAILING SCHEDULE AND OTHER CONNECTIONS.

11. IDENTIFY CEILING HEIGHTS ABOVE THE FLOOR IN ALL AREAS ON FLOOR PLAN.

STRUCTURAL PLANS:

1. SHOULD THE FRAMING FOR THE REST OF THE PORCH HAVE BEEN INCLUDED IN THIS PROJECT OR WILL THERE BE ANOTHER PERMIT LATER?

2. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. THESE TRUSSES, IF A DEFERRED SUBMITTAL, CONNOT BE WALKED THROUGH. THEY WILL HAVE TO BE SUBMITTED.

3. PLEASE ASK MR. HARRIS, ENGINEER, TO PROVIDE A PLAN WITH THE LOCATION OF THE BEAMS, POST/COLUMNS, AND LOCATION OF THE BWPs TO ACCOMPANY HIS SUBMITTAL.

4. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES.

ELEVATIONS:

1. PROVIDE AMENDED ELEVATIONS SHOWING WHAT IT WILL LOOK LIKE WITHOUT THE DELETIONS.

2. INDICATE ALL MATERIALS USED; STUCCO, CONCRETE BLOCK, GLASS BLOCK, ROOFING SYSTEMS, SIDING,
VENEERS, ETC.

3. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).

4. NOTE AND SIZE ALL ROOF DRAINS OR SCUPPERS ON FLAT-ROOFED AREA PER R903.4.

5. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

SECTIONS - DETAILS - MISC. NOTES:

1. ON STANDARD DETAIL SHEETS, CROSS-OUT ALL DETAILS THAT DO NOT APPLY OR WERE NOT USED.

2. WINDOW NOTE 9 / A1 ; THE CODE OF REFERENCE SHOULD BE THE 2003 I.R.C.

3. 3 / D1 ; PROVIDE "SW4" NAILING. I CAN'T FIND IT.

4. 3 / D1 ; PLEASE SPEC THE PINS. FOR THE PLATE / CONCRETE CONNECTION.

5. 1 / D1 ; THIS DETAIL SPEC'S #4 @ 24" OC BUT THE FOUNDATION PLAN SPEC'S #3 @ 24"OC. PLEASE RESOLVE.

6. ROOF DETAILS ; PROVIDE THE SLOPE OF THE ROOFS AND ELIMINATE THE DETAILS THAT AREN'T USED.

7. 3 / D2 ; JUSTIFY THE 2X RAFTER'S INTEGRITY WITH A ½" LAG BOLT THROUGH IT'S WIDTH. CONSIDER THE OVER HANG AND BEARING.

8. 5 / D2 ; PROVIDE FIRE BLOCKS AT THE CEILING LINE.

9. 5 / D2 ; SPECIFY THE VENT NEAR THE TOP OF THE PARAPET.

10. 6,7,8,10, 11 / D2 ; PROVIDE THE THICKNESS OF THE PLYWOOD OR SAY WHERE IT CAN BE FOUND.

11. 6,7,8 / D2 ; SPECIFY THE WALL AND CEILING COVERINGS. SEE TABLE R702.3.5 AND IT'S FOOTNOTE D .

12. 10, 14, 19 / D2 ; TRUSS MANUFACTURERS PROVIDE TRUSS / TRUSS CONNECTIONS, BUT NOT TRUSS TO OTHER MEMBERS LIKE WALLS AND BEAMS. PLEASE SPECIFY THE TRUSS HANGER.

13. 11 / D2 ; PLEASE PROVIDE A PRESSURE TREATED, OR EQUAL, PLATE.

14. 11 / D2 ; PLEASE SPECIFY THE ANCHOR BOLTS.

15. 15 / D2 ; PLEASE SPECIFY THE PENETRATION OF THE LAG BOLT INTO THE PLATES.

16. 17 / D2 ; PROVIDE THE LEDGER TO STUD CONNECTION.

17. 19 / D2 ; PLEASE SPECIFY THE TRUSS TO BEAM HANGER. TRUSS COMPANIES SPEC THE HANGERS THAT CONNECT TRUSSES TO TRUSSES.

18. PLEASE DELETE ALL UNUSED DETAILS.

PLUMBING PLANS:

1. THE FIXTURE SCHEDULE DOESN'T APPEAR TO REFLECT THIS JOB. ARE "GROUPS" OF FIXTURE UNITS IN THE UPC ? PLEASE CHECK THE FIXTURE COUNT AND THE FIXTURE UNITS.

2. PLEASE CHECK TUCSON WATER FOR THE PRESSURE RANGE AND USE THE LOW NUMBER FOR THE DESIGN PRESSURE.

3. PLEASE CHECK THE MAXIMUM DEVELOPED LENGTH.

4. ARE YOU USING UPC's APPENDIX A FOR THE WATER CALCULATIONS ?

MECHANICAL PLANS:

1. UPDATE THE MECHANICAL PLAN TO REFLECT THE REVISED PLAN.

2. CLARIFY THE "FULL LOUVERED DOOR" IN A/C #1s CONDENSING UNIT.

3. SHOW EXHAUST FAN LOCATIONS FOR BATHROOMS, WATER CLOSET COMPARTMENTS AND LAUNDRY ROOMS
IN LIEU OF OPERABLE WINDOWS, PER R303.3

4. GAS APPLIANCES SHALL COMPLY WITH CHAPTER 17 COMBUSTION AIR REQUIREMENTS. DETAIL HOW.

5. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. PLEASE CHECK THE SPACING OF THE RECEPTACLES IN THE UNNAMED ROOM BETWEEN THE FAMILY ROOM AND THE BEDROOM. SEE E3801.2.1

2. A RECEPTACLE IS REQUIRED IN THE BEDROOM BETWEEN THE DOOR TO THE PORCH AND THE UNNAMED ROOM. THE WALL APPEARS TO BE OVER 2 FEET WIDE. SEE E3801.2.2 .

3. THE RECEPTACLES APPEAR TO BE OVER SPACED IN THE BEDROOM BETWEEN THE UNNAMED ROOM AND THE MASTER BEDROOM SEE E3801

4. PROVIDE A RECEPTACLE WITHIN 3 FEET OF THE LAVATORIES. SEE E3801.6 AND E3603.4 .

5. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND BACK OF THE
DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3.

6. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND
SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE
OUTLET, PER E3801.4.1

7. RECEPTACLES APPEAR TO BE OVER SPACED IN THE LIBRARY, DINING ROOM, AND FAMILY ROOM.

8. SHOULD THE RECEPTACLE FOR THE OVEN BE A14, 18 OR A14,16 ?

9. PROVIDE TWO 20 AMP CIRCUITS FOR THE KITCHEN TOPS, EXCLUDING THE ISLAND. SEE E3603.2 .

10. PROVIDE A SWITCHED LIGHT OUTSIDE THE GARAGE "MAN DOOR". SEE E3803.3 .

11. SHOULD THE CIRCUIT FOR A/C #2 BE A4,6 OR A2,4 ?

12. ELECTRIC KEYNOTE 4 ; PROVIDE THE LANDSCAPE ELECTRICAL.

13. PROVIDE ARC-FAULT PROTECTION FOR THE BEDROOM RECEPTACLES. SEE E3802.11 .

14. THE OUTDOOR LIGHTING CODE SUBMITTED APPEARS TO BELONG TO ANOTHER JOB. PLEASE SUBMIT ONE FOR THIS JOB. PLEASE PROVIDE CUT SHEETS FOR THE OUTDOOR LIGHTING FIXTURES AND BULBS.

15. THE ELECTRICAL AND MECHANICAL PLANS SHOW DIFFERENT LOCATIONS FOR A/C #2s CONDENSING UNIT. PLEASE RESOLVE THE DISCREPANCY.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110