Permit Number: T06CM04701
Parcel: 116155110

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04701
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2006 STEVE SHIELDS ZONING REVIEW Approved
08/25/2006 GERRY KOZIOL WWM REVIEW Approved
08/29/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/29/2006 ROBERT SHERRY WATER REVIEW Approved
08/29/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE COMPLETED CODE REVIEW CHECKLIST, INCLUDING ALLOWABLE AREA CALCULATION, SEPARATED VS NON-SEPARATED USES, ALLOWABLE AREA, AND LIST CURRENT CODES PER COT/DSD WEBSITE.
S2. CLEARLY INDICATE LOCATION OF WORK ON SITE PLAN SEALED BY ARCHITECT OF RECORD.
S3. PROVIDE PROJECT COST ON PERMIT APPLICATION FORM.
S4. PROVIDE ACCESSIBILITY INFORMATION ON DRAWING #X1, SHOWING ESTIMATE OF ACCESSIBILTY COST VS TOTAL COST OF PROJECT AND EXPLAIN HOW CONFORMANCE WITH CHAPTER 11 OF 2003 IBC AND ANSI A117.1-2003ed IS ACCOMPLISHED.
S5. SHOW ADJACENT TENANT SPACE OCCUPANCY ON THE FLOOR PLAN AND SHOW SEPARATION, IF NEEDED.
08/29/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the sequence of operation for the exhaust fan in the new restroom to show that no recirculation of air will occur from the restroom.
08/29/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the drawing to show the complete scope of plumbing work.
2. Provide a shutoff valve for the new connection to the domestic water.
09/06/2006 CAGUILA1 ENGINEERING REVIEW Needs Review
09/06/2006 CAGUILA1 FIRE REVIEW Needs Review
09/06/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review