Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how adequate makeup air is to be provided for the hood (other than by opening windows). The prep room shows 600 cfm of supply air and 1400 cfm of return air so it won't be able to contribute any transfer air. Include the Type 2 hood's exhaust volume in the make up air calculations.
09/26/2007 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/26/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the specifications for the owner-provided grease trap.
2. Provide the specifications for the owner-provided prep sink.
3. Specify the type of backflow preventers to be used with P-6.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2007 GERARDO BONILLA OUT TO CUSTOMER Completed