Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM04662
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how adequate makeup air is to be provided for the hood (other than by opening windows). The prep room shows 600 cfm of supply air and 1400 cfm of return air so it won't be able to contribute any transfer air. Include the Type 2 hood's exhaust volume in the make up air calculations. |
| 09/26/2007 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/26/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the specifications for the owner-provided grease trap. 2. Provide the specifications for the owner-provided prep sink. 3. Specify the type of backflow preventers to be used with P-6. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/26/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |