Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM04662
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the installation of the 3-compartment sink on sheet P2.3 with the design shown on sheets P2.2 and P 2.4. Reference Section 103.2.3, UPC 2003. |
| 05/15/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Second request. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the make up air unit units. Reference Section 302.1, IMC 2003. 2. Second request. Coordinate the electrical requirements for MAU-1. |
| 05/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide electrical power the 3-phase fan specified on Sheet M1.1 for MAU-1. 2. The circuit for K-9, as shown on the Power Plan, appears to be new. This is identified as an existing circuit on the panel schedule. 3. Provide panel and circuit for dishwasher. Add to load calculations. Provide disconnecting means. 4. Provide receptacles for drinking fountains, and add to load calculations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/25/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 05/25/2007 | SUE REEVES | REJECT SHELF | Completed |