Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM04662
Parcel: 127022830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04662
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Second request. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the make up air unit units. Reference Section 302.1, IMC 2003.
2. Second request. Coordinate the electrical requirements for MAU-1.
05/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the installation of the 3-compartment sink on sheet P2.3 with the design shown on sheets P2.2 and P 2.4. Reference Section 103.2.3, UPC 2003.
05/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide electrical power the 3-phase fan specified on Sheet M1.1 for MAU-1.
2. The circuit for K-9, as shown on the Power Plan, appears to be new. This is identified as an existing circuit on the panel schedule.
3. Provide panel and circuit for dishwasher. Add to load calculations. Provide disconnecting means.
4. Provide receptacles for drinking fountains, and add to load calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2007 VFLORES1 OUT TO CUSTOMER Completed
05/25/2007 SUE REEVES REJECT SHELF Completed