Permit Number: T06CM04662
Parcel: 127022830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04662
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The definition of a heavy-duty cooking appliance includes "gas open-burner ranges (with or without ovens)"; a "gas hot-top range" is defined as a medium-duty appliance. Provide information to clarify the proper placement of the "gas range" called out on sheet M1.1. Reference Section 202, IMC 2003.
2. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the make up air unit units. Reference Section 302.1, IMC 2003.
3. Coordinate the electrical requirements for MAU-1.
04/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The drinking fountain, as shown on the drawings and the manufacturer's cut sheet, does not meet the accessibility requirements of ICC/ANSI A117.1-2003, which calls for a high-low drinking fountain.
2. No cut sheets for the new icemaker were received, no water supply for the new icemaker is shown on the drawings, and no power is provided for the new icemaker. Provide specifications for the new icemaker and show how it is to be installed. Reference Section 103.2.3, UPC 2003.
3. If the new 3-compartment sink is to be used as a prep sink, all of the compartments shall be indirectly wasted. Reference Section 801.2.3, UPC 2003.
4. The note referenced in the response to the plumbing comments requiring that the stops on the shower mixing valve be set to limit the water temperature to 120 degrees Fahrenheit was not found on the drawings.
5. Power for the new equipment (as noted on the architectural, mechanical, and plumbing drawings) is not shown on the electrical drawings. Revise the electrical drawings as required to coordinate the project.
05/04/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
05/08/2007 GERARDO BONILLA REJECT SHELF Completed