Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM04662
Parcel: 127022830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04662
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE CLARIFY CODE ANALYSIS FOR SITE. YOU APPEAR TO WANT TO SEPARATE THE USE OF MANAGERS QUARTERS FROM I1 OCCUPANCY. INDICATE LOCATION OF IMAGINARY PROPERTY LINE BETWEEN BUILDINGS/ USES.

2) PLEASE DIMENSION SETBACKS TO BUILDING FROM REAL AND IMAGINARY PROPERTY LINES. CLARIFY COMPLIANCE WITH 2003 IBC TABLE 602 AND 704.8.

3) CLARIFY CONSTRUCTION TYPE AND FIRE RESISTIVE REQUIREMENTS. PLEASE REFERENCE TABLE 601 AND SECTION 603 IF YOU WANT TO CLAIM TYPE 1A CONSTRUCTION. JUSTIFY HOW EXISTING STRUCTURE MEETS TABLE 601 REQUIREMENTS.

4) PROVIDE DIMENSIONED FLOOR PLAN. SCALE NOTATION ON PLAN VARIES FROM ARCHITECHTURAL AND PLUMBING PAGES.

5) BECAUSE ALL DWELLING UNITS ARE BEING OR HAVE BEEN RENNOVATED YOU MUST MEET TYPE B REQUIREMENTS PER SECTION 1107.5 OF 2003 IBC. THIS IS IN ADDITION TO PROVIDING THE 4% OF TYPE A DWELLING UNITS.

6) BOTH SHOWER ROOMS THAT WERE REMODELED WITHOUT PERMITS MUST BE FULLY ACCESSIBLE PER CHAPTER 11 OF THE IBC AND ANSI 117.1.
03/22/2007 ROBERT SHERRY WATER REVIEW Approved
03/22/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/23/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The definition of a heavy-duty cooking appliance includes gas ranges. Unless the existing hood is listed for this duty with a flow of 4,000 CFM or there are records showing that the hood was previously approved with a flow of 4,000 CFM, balance the hood per the requirements of Section 507.13.2, IMC 2003.
2. Show that the make-up air system is interlocked with the Type I exhaust system. Reference Section 508.1, IMC 2003.
3. Show how the temperature control for the kitchen area is being addressed. Reference Sections 309.1 and 508.1.1, IMC 2003.
4. Show how ventilation is being provided to the restrooms. Reference Section 403.3, IMC 2003.
03/30/2007 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/02/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
04/02/2007 SUE REEVES REJECT SHELF Completed