Permit Number: T06CM04662
Parcel: 127022830

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04662
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2006 MARTIN BROWN FIRE REVIEW Approved
08/25/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/29/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide the minimum plumbing fixtures required per Table 2902.1, IBC 2003.
3. Provide specifications for the new dishwasher and show how it is to be installed. Reference Section 103.2.3, UPC 2003.
4. Provide specifications for the new icemaker and show how it is to be installed. Reference Section 103.2.3, UPC 2003.
5. Provide fixture descriptions for all new plumbing fixtures (e.g. sinks for the kitchen). Explain how the new 3-compartment sink is to be used Reference Sections 103.2.3,401.1, UPC 2003.
6. Provide additional information to show how the new shower pans comply with the construction and installation requirements of section 412.0, UPC 2003.
7. Show how the mixed water temperature is to be limited for the showers. Reference Section 420.0, UPC 2003.
8. Show how the discharge water temperature is to be limited for the bathtubs. Reference Section 421.0, UPC 2003.
9. One of the specified fixtures (Pegasus water closet) requires a minimum pressure greater than 15-PSI. Provide information to show that the existing water distribution system can supply suitable water pressure at the projected demand. Reference Section 608.1, UPC 2003.
10. Provide waste and vent isometrics for all of the new waste and vent piping. Reference Section 103.2.3, UPC 2003.
11. Provide upper terminal cleanouts for all of the new waste piping per Section 707.4, UPC 2003.
12. Revise the trap arm length for the new tub, F4, to conform to Table 10-1, UPC 2003. Reference Section 1002.2, UPC 2003.
13. Verify the input rating for the clothes dryers. Reference Section 1209.4.2, UPC 2003.
14. Revise the developed lengths of the natural gas pipes to coordinate with the drawings. Reference Section 103.2.3, UPC 2003.
15. Revise the size of the natural gas pipes per Section 1217.1, UPC 2003 or provide calculations demonstrating conformance to Section 1217.3, UPC 2003. (Note that the input for natural gas appliances is expressed in BTU/H)
16. Provide listing information for the relocated grease trap that shows it has been designed for a 2" outlet. Reference Section 103.2.3, UPC 2003.
17. Provide a vent to protect the grease trap from siphonage and backpressure. Reference Section 1002.1, UPC 2003.
18. A dishwasher shall not discharge or be connected to a grease trap. Reference Section 1015.0, UPC 2003.
19. Floor sinks and floor drains can't be connected to a grease trap. (The flow control device for a grease trap must be installed in a location that is readily accessible and visible.) Reference Section 1014.3, UPC 2003.
08/29/2006 ROBERT SHERRY WATER REVIEW Denied Show the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control.
08/29/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a Type I or Type II hood, as appropriate, over all commercial cooking or heat-producing appliances. Reference Section 507.2, IMC 2003.
09/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide electrical power for the spa.
2. Provide electrical power for the new dishwasher.
3. Provide electrical power for the new ice machine.
4. Indicate whether walk-in fridg is new or existing.
5. Indicate whether walk-in cooler is new or existing.
6. Indicate whether steamer is new or existing, and whether it needs electrical power.
7. If new bathroom fans are to be installed, provide electrical power.
8. Address electrical circuiting for new lighting fixtures, and electrical loads.
09/18/2006 GERRY KOZIOL WWM REVIEW Approved
09/20/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 9/27/06
ACTIVITY NUMBER: T06CM04662
PROJECT NAME: Adult Care Center
PROJECT ADDRESS: 1020 N. Woodland Ave
ARCHITECT / ENGINEER: Therese Brown
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CHRISTY.FOREMAN@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.



1) Clarify occupancy I1 or I2 based on last 2 C of O's this facility was classified as a I2 Nursing Home.
2) Clarify occupant load for each room.
3) Laundry Room originally a Master Bathroom. Show all modifications made.
4) All restroom fixtures shall be accessible.
5) Chapel converted to Beauty salon show the revisions that have been made.
6) Detail new accessible ramps shown per ANSI A117.1 2003.
7) Bathroom converted to storage room south of walk-in cooler.
8) Show administrative area removed.
9) Wall added to create pantry provide appropriate details.
10) Shower room and Handicap shower room 2 water closets removed - 1 tub relocated - 2 showers added. Show scope of work in this area.
11) Clarify exit lighting / signs.
12) Specify / clarify fixtures per Table 2902.1.
13) Justify per 3407.7.7 2003 IBC
14) Bathroom fixtures - clarify/justify how this is included in 20% cost of construction towards providing accessibility. Provide details with dimensions for all accessible items added.
15) Clarify accessible route

16) Provide Drinking fountains and spout heights and water flow ANSI 602.4 and 602.6.
17) Visual alarms in rest rooms ANSI 702.1.
18) Toilet lever on closed side ANSI 604.10.6
19) Door latch side clearance ANSI 404.2.3
20) Van space and access aisle widths ANSI 502.2, 502.4
21) Cane delectability of protruding objects ANSI 307.
22) Door opening force ANSI 404.2.8
23) Transfer shower size and layout ANSI 607 and 608
24) Hot water contact under sink ANSI 606.6
25) Ramp edge barrier ANSI 405.9
26) Sign height 7' at parking TDOT regulations

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
10/06/2006 SUE REEVES REJECT SHELF Completed