Permit Number: T06CM04661
Parcel: 127022830

Address:
5419 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04661
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2006 MARTIN BROWN FIRE REVIEW Denied Ocupancy is not R-1 as indicated on code review sheet.
Occupancy is R-2 and B. Because of change of use, fire sprinklers required.
2003 IFC, Chapter 2, Definitions
2003 IFC, Section 903.2.7
08/24/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide fixture descriptions for all new plumbing fixtures. Reference Section 401.1, UPC 2003.
2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
3. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 504.7, IECC 2003.
4. Show how the maximum mixed water temperature is to be limited for the shower. Reference Section 420.0
5. Revise the size of the main natural gas pipe per Section 1217.1, UPC 2003 or provide calculations demonstrating conformance to Section 1217.3, UPC 2003. (Note that the input for natural gas appliances is expressed in BTU/H and the demand is expressed in CFH.)
08/24/2006 ROBERT SHERRY WATER REVIEW Denied Show the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control.
08/24/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the size, routing, and termination of the condensate drain from the air coil. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003.
08/25/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/18/2006 GERRY KOZIOL WWM REVIEW Approved
09/20/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
10/06/2006 GERARDO BONILLA REJECT SHELF Completed