Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04661
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | Ocupancy is not R-1 as indicated on code review sheet. Occupancy is R-2 and B. Because of change of use, fire sprinklers required. 2003 IFC, Chapter 2, Definitions 2003 IFC, Section 903.2.7 |
| 08/24/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide fixture descriptions for all new plumbing fixtures. Reference Section 401.1, UPC 2003. 2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003. 3. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 504.7, IECC 2003. 4. Show how the maximum mixed water temperature is to be limited for the shower. Reference Section 420.0 5. Revise the size of the main natural gas pipe per Section 1217.1, UPC 2003 or provide calculations demonstrating conformance to Section 1217.3, UPC 2003. (Note that the input for natural gas appliances is expressed in BTU/H and the demand is expressed in CFH.) |
| 08/24/2006 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control. |
| 08/24/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the size, routing, and termination of the condensate drain from the air coil. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003. |
| 08/25/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/08/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/18/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/20/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/06/2006 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 10/06/2006 | GERARDO BONILLA | REJECT SHELF | Completed |