Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM04659
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2007 | LINHART PETERSEN POERS ASSOC. | 2ND PARTY REVIEW | REVIEW | Denied | January 5, 2007 CITY OF TUCSON - THIRD CHECK Tucson Appl. No. T06CM04659 Bureau Veritas Job No. 2060161.057 Mr. Adrian Zitzmann 2292 W. Magee # 220 E. Seneca Tucson, Arizona 85742 Re: Plan Review: Zitzmann Residence Address: 10808 E. Placita Marimba Dear Mr. Zitzmann: Bureau Veritas North America has completed a review of the following documents on behalf of the City of Tucson: Plans: Two (2) copies of plans (11 sheets, 1 through 8) dated September 11, 2006 by Bruce O. Kelly. Structural Calculations: Two (2) copies of calculations dated September 11, 2006 by Bruce O. Kelly. Soils Letter/Report: Two (2) copies of soils report dated March 16, 2006 by E.L. Vick of Southern Arizona Testing Laboratory. Energy Compliance: Two (2) copies of REScheck Compliance Certificate 2003 IECC dated July 20, 2006. These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC). Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded. Sincerely, BUREAU VERITAS NORTH AMERICA Shelley Knuffke ICC Plans Examiner SK:pc F:\Tucson\01006-161057pc3.doc enclosures A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code. B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance. C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.). GENERAL COMMENTS: Provide an accurate index to drawings on the first sheet of the set. No taped on information will be accepted. The data must be delineated on the drawings as part of the original tracings or masters. FLOOR PLAN: Show that each water closet is located in a clear space not less than shown in IRC Figure 307.2. Show dimensions of water closet at bath 2. MECHANICAL: Show condensate line and secondary condensate line. IRC Sec. M1411.3 and M1411.3.1. If you have any questions regarding the above comments, please contact Shelley Knuffke at (520) 576-8400 between 8:00 A.M. to 5:00 P.M., M-F. |