Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04651
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/21/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify how the condensate is to be drained from the fan coil units - pumped or gravity flow. 2. Show how secondary drainage is to be provided for the fan coils. 3. Show how and from what the fan coils are to be supported. |
| 08/21/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/21/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/21/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 08/22/2006 | HEATHER THRALL | ZONING | REVIEW | Passed | |
| 08/22/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/30/2006 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 08/30/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1) PROVIDE SRUCTURAL CALCULATION FOR NEW MECHANICAL UNITS BEING SUPPORTED ABOVE CEILING. |