Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04626
Parcel: 117061900

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04626
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) THE KITCHEN HOOD NEEDS TO BE PERMITTED AND JUSTIFIED.
2) INCLUDE HOOD IN COST OF CONSTRUCTION.
09/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04626 N 9/12/06

1. Receptacle is on Ckt A-15 according to the Power Plan. On the Panel Schedule, this is for Panel B.
2. Please clarify what Ckt A-17 is powering on the Power Plan. No such electrical load on Panel Schedule.
3. Please coordinate electrical requirements with Mechanical and clarify. Mechanical 208V, Electrical 240V.
09/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the make up air unit can have a minimum heating capacity of 120 MBH with a maximum natural gas input of 100 CFH.
10/09/2006 CAGUILA1 WWM REVIEW Needs Review