Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/21/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) THE KITCHEN HOOD NEEDS TO BE PERMITTED AND JUSTIFIED. 2) INCLUDE HOOD IN COST OF CONSTRUCTION. |
09/21/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04626 N 9/12/06 1. Receptacle is on Ckt A-15 according to the Power Plan. On the Panel Schedule, this is for Panel B. 2. Please clarify what Ckt A-17 is powering on the Power Plan. No such electrical load on Panel Schedule. 3. Please coordinate electrical requirements with Mechanical and clarify. Mechanical 208V, Electrical 240V. |
09/21/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the make up air unit can have a minimum heating capacity of 120 MBH with a maximum natural gas input of 100 CFH. |
10/09/2006 | CAGUILA1 | WWM | REVIEW | Needs Review |