Permit Number: T06CM04626
Parcel: 117061900

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM04626
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE ACCURATE BUDGET FOR VALUATION. INCLUDE COST OF STRUCTURAL.
2) IT APPEARS THERE IS A CONFLICT WITH BEAM AND COLUMN LOCATION AND NEW DUCT WORK.
3) PROVIDE SECTION SHOWING MECHANICAL LOAD AND HOW IT IS CARRIED DOWN TO SLAB FOOTING.
09/20/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied See previous comments. Plans do not appear to have changed.
09/20/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vent and cleanout for the new grease trap.
2. Provide a diagram of the gas piping to show the total connected loads and developed lengths of the piping. The required information for the existing equipment is not shown on the drawing.
3. Show how the make up air unit can have a minimum heating capacity of 120 MBH with a maximum natural gas input of 100 CFH.
09/21/2006 DROBEY1 WWM REVIEW Needs Review