Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04624
Parcel: 11451216G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04624
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
08/17/2006 CHRISTY FOREMAN MECHANICAL-COMMERCIAL REVIEW Passed
08/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04624 8/17/06

Panel A is slated for replacement according to the Power Demolition. However, it is shown as existing on the Power Plan, Riser Diagram, and Panel Schedule. Please clarify. There could be a concern because it is about 35' from the service, which would have a TEP AFC of 55,600A.
2. If this panel is rated for 150A, it would not be properly protected by a 200AF. Same concern about the 100A feeder.
08/17/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
08/17/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/17/2006 CHRISTY FOREMAN PLUMBING-COMMERCIAL REVIEW Approved
08/17/2006 MARTIN BROWN FIRE REVIEW Approved
08/25/2006 DROBEY1 WWM REVIEW Needs Review
08/25/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/25/2006 DROBEY1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2006 DELMA ROBEY APPROVAL SHELF Completed
08/25/2006 DELMA ROBEY OUT TO CUSTOMER Completed
08/25/2006 DELMA ROBEY REJECT SHELF Completed