Permit Number: T06CM04622
Parcel: 106121250

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04622
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2006 MARTIN BROWN FIRE REVIEW Approved
08/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04622 8/17/06

1. Provide a maintenance receptacle for the Heat Pump. Reference NEC 210.63.
2. Provide a lighting fixture schedule.
3. Demonstrate compliance with the Tucson Lighting Code.
4. Provide available fault current at the electrical service.
5. Provide fault current rating of new panel.
6. Demonstrate that new panel is installed within its fault current rating.
7. Bathroom receptacles for each bathroom shall supply no other outlet. Reference NEC 210.11 (C) (3).
8. Bedroom branch circuits shall have AFCI. Reference NEC 210.12.
9. Meet receptacle spacing requirements per NEC 210.52 (A) (1).
10. Meet receptacle spacing requirements per NEC 210.52 (C) (1).
08/17/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Minimum font size 1/8"
08/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise drawings for legibility, minimum font size of 1/8", and show riser diagrams for the waste and water supply systems.
2. Show that the shower valve is pressure balanced.
3. Show how the hot water temperature to the shower is to be limited to 120 degrees Fahrenheit. (The thermostat of the water heater may not be used to assure the maximum temperature.)
4. Show how the T&P relief for the water heater can be routed to the outside of the building.
08/21/2006 ROBERT SHERRY WATER REVIEW Denied Show that a backflow protection valve is not required for this building.
09/01/2006 CAGUILA1 ZONING REVIEW Needs Review
09/01/2006 CAGUILA1 WWM REVIEW Needs Review
09/01/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/01/2006 ANY ENGINEERING REVIEW Approved