Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM04613
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2007 | DAVE MANN | FIRE | REVIEW | Denied | Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
| 05/16/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | 1:best buy 2:needs to show location/method of connection to public sewer-need to permit on-site private sewer |
| 05/18/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/22/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/22/2007 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/28/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 06/28/2007 | SUE REEVES | REJECT SHELF | Completed |