Review Details: RESUBMITTAL - SITE ALL
Permit Number - T06CM04598
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2007 | DAVE MANN | FIRE | REVIEW | Denied | 6 feet clear (no roof) between new and existing duplex will be required or provide automatic fire sprinkler system. Sheet A4 shows the buildings connected and windows and openings in the walls. |
| 09/04/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/05/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | The location of the truncated domes are not in the correct location as depicted on the plan view. Detectable warnings (truncated domes) are required at marked crossings (crosswalks). The area covered by the truncated domes shall be twenty-four (24) inch deep and extend the full width of the crosswalk/ramp. All accessible curb ramps shall have truncated domes installed that shall be twenty-four (24) inches minimum in the direction of travel and extend the full width of the curb ramp or flush surface. The domes shall be located so the edge nearest the curb line is six (6) inches to eight (8) inches from the curb line. ANSI 406.12, ANSI 705 |
| 09/11/2007 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. A 10' interior landscape border is required along site boundaries of the adjacent residential property to the south per LUC Table 3.7.2-I. One (1) canopy tree must be provided for every thirty-three (33) linear feet of the Interior Landscape Border per LUC 3.7.2.4. 2. A 5' wall is required to screen residential properties from vehicle use area per LUC Table 3.7.2-I. All walls required by this Division must be of masonry material or masonry with stucco or textured finish. Variances are necessary for LUC requirements remove reference to DDO process on the landscape plan. 3. Include with re-submittal approval documentation. Indicate on the lower right hand corner of the site plan, the variance case number, date of approval, and any conditions imposed. 4. Additional comments may apply. |
| 09/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 D of the Arizona Administrative Code states that a registrant shall sign, date, and seal professional documents that are to be submitted to any regulatory or review body. 2. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2003, as amended by the City of Tucson. |