Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/20/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CODE ANALYSIS DATA SHEET. 2) CLARIFY OCCUPANCY 3) CLARIFY TENANT SPACE LOCATION ON SITE PLAN. 4) CLARIFY SEPARATED OR NON-SEPARATED USE. 5) PROVIDE WALL SECTION 6) CLARIFY AND JUSTIFY RESTROOM FACILITIES. PROVIDE PATH OF TRAVEL AND DISTANCE FROM SUITE TO PUBLIC RESTROOMS. PROVIDE FIXTURE LAYOUT OF RESTROOM IN THE SUITE. LABEL EACH ROOM FOR OCCUPANCY TYPE. 7) PROVIDE STRUCTURAL CALCULATIONS TO JUSTIFY NEW MECHANICAL UNIT. |
03/20/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/20/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the model number of the proposed heat pump, including the installed weight. Show that the existing roof can support the new unit. 2. Show the size, route, and termination of the condensate drain for the heat pump. 3. Correct the outside air calculations; 20 CFM per person is required for conference rooms. |
04/16/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/16/2007 | DROBEY1 | ZONING | REVIEW | Needs Review | |
04/16/2007 | DROBEY1 | FIRE | REVIEW | Needs Review | |
04/16/2007 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
04/16/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/16/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |