Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM04586
Parcel: 11520007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04586
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CODE ANALYSIS DATA SHEET.
2) CLARIFY OCCUPANCY
3) CLARIFY TENANT SPACE LOCATION ON SITE PLAN.
4) CLARIFY SEPARATED OR NON-SEPARATED USE.
5) PROVIDE WALL SECTION
6) CLARIFY AND JUSTIFY RESTROOM FACILITIES. PROVIDE PATH OF TRAVEL AND DISTANCE FROM SUITE TO PUBLIC RESTROOMS. PROVIDE FIXTURE LAYOUT OF RESTROOM IN THE SUITE. LABEL EACH ROOM FOR OCCUPANCY TYPE.
7) PROVIDE STRUCTURAL CALCULATIONS TO JUSTIFY NEW MECHANICAL UNIT.
03/20/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/20/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the model number of the proposed heat pump, including the installed weight.
Show that the existing roof can support the new unit.
2. Show the size, route, and termination of the condensate drain for the heat pump.
3. Correct the outside air calculations; 20 CFM per person is required for conference rooms.
04/16/2007 ROBERT SHERRY WATER REVIEW Approved
04/16/2007 DROBEY1 ZONING REVIEW Needs Review
04/16/2007 DROBEY1 FIRE REVIEW Needs Review
04/16/2007 DROBEY1 ENGINEERING REVIEW Needs Review
04/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2007 DELMA ROBEY OUT TO CUSTOMER Completed