Permit Number: T06CM04586
Parcel: 11520007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04586
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2007 CAGUILA1 ZONING REVIEW Needs Review
03/20/2007 CAGUILA1 ENGINEERING REVIEW Needs Review
03/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/20/2007 CAGUILA1 FIRE REVIEW Needs Review
12/19/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the model number of the proposed heat pump, including the installed weight. Show that the existing roof can support the new unit.
2. Show the size, route, and termination of the condensate drain for the heat pump.
12/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04586 12/19/06

1. HP-1 has 208V power on the Electrical plans. Mechanical calls for 230V. Coordinate with Mechanincal and clarify.
2. Please enter the load for the Projector on the panel schedule.
12/19/2006 ROBERT SHERRY WATER REVIEW Approved
12/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CODE ANALYSIS DATA SHEET.
2) CLARIFY OCCUPANCY
3) CLARIFY TENANT SPACE LOCATION ON SITE PLAN.
4) CLARIFY SEPARATED OR NON-SEPARATED USE.
5) PROVIDE WALL SECTION
6) CLARIFY AND JUSTIFY RESTROOM FACILITIES.
12/19/2006 RSHERRY1 WWM REVIEW Passed
12/19/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed