Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04546
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2006 | ANY | ENGINEERING | REVIEW | Approved | Restamp for zoning change. Original stamped off by Paul M. 8/24/06 |
| 08/24/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04546 8/24/06 Provide a load calculation for the panel and feeder. Demonstrate that no phase is overloaded. |
| 08/24/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the plumbing plan, water, and waste riser diagrams to coordinate with the actual conditions (e.g. where is the urinal ?). 2. Revise the water calculations to include the urinal (20 fixture units per Table 6-5). 3. Does the existing water heater have an expansion tank? |
| 08/24/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/25/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/25/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | Provide engineering calc`s for safety steel cage connections. |
| 08/29/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 08/29/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/29/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/29/2006 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 08/29/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/29/2006 | DELMA ROBEY | REJECT SHELF | Completed |