Permit Number: T06CM04539
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04539
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2006 TERRY STEVENS ZONING REVIEW Approved
08/11/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04539 8/11/06

1. For Ckts 202-14,16,18, and 202-7,9,11, indicate the intent of the J-boxes. Future receptacles for modular furniture, or what?
2. The item on Ckts 202-8,10,12 is unclear. Please add this symbol to the Electrical Symbols, and clarify description on panel schedule as necessary.
3. With TEP high demand of 270.5 KW, or 883.3A at 0.85 pf, (883.3) (1.25) = 1104A. 1104 + 66 = 1170. This exceeds the 1155A ampacity of the service entrance conductors. Please carry through this entire calculation on the plans, and demonstrate Code-compliance. Suggest that you subtract the fixtures and receptacles slated for demolition to this end.
08/11/2006 ROBERT SHERRY WATER REVIEW Approved
08/11/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/11/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
08/11/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/11/2006 DAVE MANN FIRE REVIEW Approved
08/17/2006 CAGUILA1 WWM REVIEW Needs Review
08/17/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review