03/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Panel D has loads removed on Ckts 36,38,40,42, with no Revision cloud. Please clarify.
2. Changes were made in Panel F (UPS3) without Revision cloud. Please clarify.
3. Identify changes in Panel PA2, A, B, and C, using Revision cloud.
4. One-line diagram printed out without showing all of the electrical lines and devices.
5. Will re-evaluate load calculations after any and all changes in panelboards as noted above have been documented as such on the revised plans, as noted above.
03/29/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/23/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved