Permit Number: T06CM04531
Parcel: 140420190

Address:
2711 E ELVIRA RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04531
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
08/11/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
2. Clarify the number of water closets and urinals used in the ventilation calculations for this building; 14 are identified in the calculations but 15 are shown on the plans.
3. Show how access to the rooftop equipment is to be provided. Reference Section 306.5, IMC 2003.
08/11/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference Section 103.2.3, UPC 2003.
2. Show upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 2003.
08/11/2006 ROBERT SHERRY WATER REVIEW Approved
08/14/2006 DAVE MANN FIRE REVIEW Approved
08/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide a detail for the mounting of New Transformer T9, and structural calculations, prepared, sealed, and signed by a Structural Engineer registered in the State of Arizona.
2. Please demonstrate that X'FMR T10 is protected according to the requirements of NEC 450.3.
3. Sheet E503 Keynote 2, the #1 GND is properly sized at 2/0. Reference NEC Table 250.66.
4. Account for T10 and Panel PA2E electrical load on Panel Schedule PA2.
5. There is a panel schedule for UPS2, but no such panel on the line diagram. Note that Panel G (UPS2) is represented on the line diagram and panel schedule. Please clarify.
08/28/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06CM04531 .. 2711 EAST ELVIRA ROAD .. REMODEL OFFICE FOR UNIVERSITY PHYSICIANS HEALTHCARE .. DGL .. IST REVIEW .. 9/1/06 ..

TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

Provide a Response Letter, by the Registrant of Record, with the re-submittal addressing each comment listed in Structural Review.

S1. Provide completed Code Review Checklist, as required by 1997 Uniform Administrative Code Section 302.1, including: Job Address, Architect, Signature, Date, Summary of Governing Regulations, General Building Summary and Allowable Area Calculation for this address 2711 East Elvira Road. See DSD website : www.tucsonaz.gov/dsd, for form.
S2. Provide revised drawing G0.02 showing accessibility fixture heights and locations conforming to Chapter 11 and 34 of the 2003 IBC and ANSI A117.1-2003 ed.
S3. Provide Project Cost for the Permit for this building and show on drawing G0.01 an estimate explaining where 20% of the Project Cost for this building is spent on accessibility or the building is brought into conformance with the 2003 IBC Section 11 and 34 and ANSI A117.1-2003 ed.
S4. Detail on the drawings where conformance to the accessibility requirements of IBC Section 11 and 34 and ANSI A117.1-2003 ed are provided, showing how requirements are met and indicate Accessible Route.
S5. Indicate, on drawings, the existing Occupancy and Type of Construction for existing buildings on site, per IBC Sections 3 and 6, respectively, also indicate the Location, Type of and Fire-rating of existing Fire Walls on site, explaining if and how they are or are not to be maintained for the purposes of this Permit, per IBC Section 7.
S6. Clarify/revise drawing G0.04, this drawing has references to in Code Summary to the UBC, as the City of Tucson's current Building Code is the 2003 IBC update these references to the 2003 IBC and verify that the remainder of this design conforms to the 2003 IBC.
S7. Dimensionally locate, from two adjacent roof edges, new roof-mounted equipment on the Roof Plan drawing A1.11, including Sonotube Skylights and New Mechanical Unit.
S8. Clarify on drawing A4.02, Interior Finishes conformance with IBC Section 8, including Kraft Paper by listing Flame-spread and Smoke-development Wall and Ceiling Finishes per Section 803 and Table 803.5.
S9.Locate drinking fountain/s per IBC Section 29 and Table 2902.1, also address accessibility of drinking fountain/s, on drawing A1.02.
S10. Clarify how Means of Egress Illumination conforms to IBC Section 1006, ie: exterior exit lighting.
S11. Manual sliding doors do not appear to comply with IBC Section 1008, 1008.1.2 exc 5, 1008.1.1.3, provide complying sliding doors or revise drawing to conform.
S12. Clarify Exit Doors and Hardware conform to requirements of IBC Section 10 and 11:
1. Door #200.
2. Door #209.
3. Door #219A, Hardware Schedule on drawing A0.02 HW is #15 but Specifications indicate Hardware Set #1?
4. Door #247.
5. Door #248A.
Please comment.
S13. Provide Structural Calculations for :
1. Check existing roof structure capacity to support new ceiling, mechanical, electrical, fire sprinklers or other loads.
2. New canopies to replace existing at two locations on this building.
S14. Provide Special Inspection for:
1. Field Welding.
2. Shop Welding.
3. Expansion Anchors.
4. Epoxy Anchors.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.
09/06/2006 GERRY KOZIOL WWM REVIEW Denied needs 8th floor wastewater credit evaluation

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
09/13/2006 SUE REEVES REJECT SHELF Completed