Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04524
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide wall section - for seismic bracing per section 1621 to clarify wall and ceiling act independant or justify with structural calculations that 1621.1.2 Exception load does not excee 5 psf |
| 09/19/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The filter fan modules do not appear to be listed and labeled. Provide listed aqd labeled appliances or comply with the requirements of Section 105, IMC 2003. Reference Section 301.4, IMC 2003. 2. Third request: the minimum font size for drawings is 1/8", all upper case. See sheet ME0.00. |
| 09/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/11/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |