Permit Number: T06CM04524
Parcel: 14041015A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04524
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide wall section - for seismic bracing per section 1621 to clarify wall and ceiling act independant or justify with structural calculations that 1621.1.2 Exception load does not excee 5 psf
09/19/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The filter fan modules do not appear to be listed and labeled. Provide listed aqd labeled appliances or comply with the requirements of Section 105, IMC 2003. Reference Section 301.4, IMC 2003.
2. Third request: the minimum font size for drawings is 1/8", all upper case. See sheet ME0.00.
09/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/11/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review