Permit Number: T06CM04524
Parcel: 14041015A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04524
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04524 8/30/06

1. Provide overucrrent protection for new panel feeder.
2. Provide AIC rating of new panel.
3. Provide available fault current at new panel.
4. Fan filter unit power cords with plugs may not be installed above the ceiling. Reference NEC 400.8 (5).
08/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide listing information for the motorized filter fans showing that they are approved
for use within a plenum.
2. Provide information to clarify the low sidewall returns (keynote 2, M-102), including
grille sizes and balancing data.
3. The minimum font size is 1/8", all uppercase.
09/19/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
09/19/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review