Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04524
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04524 8/30/06 1. Provide overucrrent protection for new panel feeder. 2. Provide AIC rating of new panel. 3. Provide available fault current at new panel. 4. Fan filter unit power cords with plugs may not be installed above the ceiling. Reference NEC 400.8 (5). |
| 08/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listing information for the motorized filter fans showing that they are approved for use within a plenum. 2. Provide information to clarify the low sidewall returns (keynote 2, M-102), including grille sizes and balancing data. 3. The minimum font size is 1/8", all uppercase. |
| 09/19/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 09/19/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |